Chapter 9 Communicate with PanelView Terminals
Logix5000 Controller Combinations
Make sure to:
· set the IP addresses for the controller’
s EtherNet/IP communication
module and the HMI terminal.
· connect all wiring and cabling
.
Connections to PanelView
Terminals
To establish communication between a PanelView or PanelView Plus terminal,
specify controller connections.
When communicating implicitly (PanelView term
inals only), the controller
uses one connection for each terminal. Make sure to account for these
connections when designing the system. The Logix5000 controllers:
· fir
mware revisions 11 and earlier support up to 16 bidirectional implicit
buffers (c
onnections).
· firmware revisions 12 or later support up to 32
bidirectional implicit
buffers (connections).
Choosing a Communication Module
Controllers Communication Modules
1756 ControlLogix 1756-ENBT, 1756-EN2F, 1756-EN2T,
1756-EN2TR, or 1756-EN2T
XT
communication modules
1768 CompactLogix 1768-ENBT communication module
1769-L23E-Q1B, 1769-L23E-QBFC1B,
1769-L32E, or 1769-L35E CompactLogix
A built-in EtherNet/IP port
1794 FlexLogix 1788-ENBT EtherNet/IP communication
module
PowerFlex 700S with DriveLogix 1788-ENBT EtherNet/IP communication
module
PanelView Terminal Connections
Type of Communication
Terminal Type
PanelView PanelView Plus
Implicit (connected)
Logix controller communicates to the PanelView terminal like an I/O module.
You must add the PanelView terminal to the I/O configuration tree for the controller project.
Supported Not supporte
d
Explicit (unconnected)
Communication is set up in PanelBuilder or RSV
iew ME software.
All communication is initiated by the PanelVi
ew or PanelView Plus terminal.
Supported Supported