User manual

Publication ENET-UM001I-EN-P - January 2010 179
Status Indicators Appendix A
Packaged Controller Status Indicators
Indicator Status Description
RUN Off The packaged controller is in program or test mode.
Steady green The packaged controller is in run mode.
FORCE Off Either:
No tags contain I/O forc
e values.
I/O forces are inactive (disabled).
Steady amber Eith
er:
I/O forces are active (enabled).
I/O forces values may or may not exist.
Flas
hing amber One or more input or output addresses have been forced to an On or Off
condition, but the forces have not be
en enabled.
BATT
Off The battery supports memory.
Steady red The battery is either:
not installed.
95% dischared and should be replaced.
I/O
Off Either:
There are no devices in the I/O confi
guration of the packaged controller.
The packaged controller does not contain a project.
Steady green The packaged
controller is communicating with all the devices in its I/O
configurat
ion.
Flashing green One or more devices in the I/O configuration of the packaged controller are not
res
ponding.
Flashing red Either:
The packaged controller is not communicating with any devic
es.
The packaged controller is faulted.