User manual

Publication ENET-UM001I-EN-P - January 2010 65
Configure a Supervisor on a Device-level Ring Network Chapter 5
Configure a Ring Supervisor in RSLogix 5000
Programming Software
To configure the 1756-EN2TR module or the 1783-ETAP, 1783-ETAP1F or
1783-ETAP2F taps as a ring supervisor, use the device’s Add-on Profile
(AOP) in RSLogix 5000 programming software, version 17.01.
To download AOP’s, go to:
http://support.rockwellautomation.com/controlflash/LogixProfiler.asp
Depending on the firmware revision of your product, you must use a specific AOP version.
For both the 1756-EN2TR module and 1783-ETAP tap, make sure that the
Major Revision configured on the
General tab of the device’s RSLogix 5000 programming software configuration matches the major revision
of the physical module.
If the device configuration on the General tab does not match the physical module, the programming
software
alerts you to this mismatch when you attempt to configure the Internet Protocol, Port
Configuration and Network tabs for that device.
Cat. No. Firmware Revision Required Add-on Profile
Revision
1756-EN2TR
2.1
(1)
(1)
You can use the ControlFLASH Firmware Upgrade software to upgrade a 1756-EN2TR module from firmware revision 2.1 to 3.x or later.
1.x or later
3.x or later 2.x or later
1783-ETAP
1.1
(2)
(2)
You can use the ControlFLASH Firmware Upgrade software to upgrade a 1783-ETAP tap from firmware revision 1.1 to 2.x or later.
To download new firmware, go to:
http://www.rockwellautomation.com/support/americas/index_en.html
If you upgrade the firmware revision on your module or tap, you must use the required AOP revision listed above for that revision. For
example, if you upgrade your 1756-EN2TR module to firmware revision 3.x or later, you must use AOP revision 2.x or later in your RSLogix
5000 programming software.
Additionally, if you upgrade the firmware revision on your module or tap, you must also use the required RSLinx communication software
for that firmware revision. For more information on which RSLinx communication software version is required for each firmware revision,
see
page 71
.
1.x or later
2.x or later 2.x or later
1783-ETAP1F 2.x or later 2.x or later
1783-ETAP2F