User manual

66 Publication ENET-UM001I-EN-P - January 2010
Chapter 5 Configure a Supervisor on a Device-level Ring Network
To configure the ring supervisor in RSLogix 5000 programming software,
follow these steps.
1. Add the module to your project.
a.
Right-click 1756 Backplane and choose New Module.
IMPORTANT
The steps to configure a ring supervisor via software are
basically the same for the 1756-EN2TR module and the
1783-ETAP, 1783-ETAP1F, and 1783-ETAP2F taps. This example
shows how to configure the 1756-EN2TR module.
You need to configure only the 1783-ETAP, 1783-ETAP1F, and
1783-ETAP2F taps in your I/O Configuration if you plan to
enable the tap as a ring supervisor. If you do not plan to use the
tap as a ring supervisor, we recommend that you do not add it
to your I/O Configuration.
Additionally, if you want to configure a 1783-ETAP,
1783-E
TAP1F, or 1783-ETAP2F tap as a supervisor via software
or with its DIP switchs, you must first assign it an IP address.
The tap does not require an IP address if it is used as a ring
node or has its supervisor function enabled by DIP switch
For more information on how to use a tap’s switch to configure
it a
s a ring supervisor, see the EtherNet/IP Embedded Switch
Technology Application Guide, publication
ENET-AP005
.
a