Specifications

7
Publication 17472.30 February 1996
Output Specifications
Description Specification
Type Relay MOSFET Triac
Voltage
5 to 264V ac
5 to 125V dc
20.4 to 26.4V dc 85 to 264V ac
Maximum Load Current
Refer to the Relay
Contact Rating Table.
1.0A per point @ 55° C (131° F)
1.5A per point @ 30° C (86° F)
0.5A per point
Minimum Load Current 10.0 mA 1 mA 10.0 mA
Current per Controller 1440 VA
3A for L16BBB
6A for L32BBB
1440 VA
Current per Common 8.0A
3A for L16BBB
6A for L32BBB
2.5A
Maximum Off State
Leakage Current
0 mA 1 mA
2 mA @ 132V ac
4.5 mA @ 264V ac
Off to On Response 10 ms max. 0.1 ms
8.8 ms @ 60 Hz
10.6 ms @ 50 Hz
On to Off Response 10 ms max. 1 ms 11.0 ms
Surge Current per Point Not Applicable
3A for 10 ms
10A for 25 ms
Repeatability is once every 2 seconds at 55°
C (131
° F).
Relay Contact Rating Table
Maximum
Volts
Amperes
Amperes
VoltAmperes
Volts
Make
Break
Continuous
Make Break
240V ac 7.5A 0.75A 2.5A 1800 VA 180 VA
120V ac 15A 1.5A
125V dc
0.22A
1.0A 28 VA
24V dc
1.2A
2.0A 28 VA
For
DC voltage applications, the make/break ampere rating for relay contacts can be determined by dividing
28 V
A by the applied DC voltage. For example, 28 V
A ÷ 48V dc = 0.58A. For DC voltage applications less
than 48V
, the make/break ratings for relay contacts cannot exceed 2A. For DC voltage applications greater
than 48V
, the make/break ratings for relay contacts cannot exceed 1A.
HandHeld Programmer Specifications
Description Specification: 1761HHPB30
Operating Power 83 mA @ 24V dc
Operating Temperature
0° C to 50° C (32° F to 122° F)
Storage Temperature
-20° C to 60° C (-4° F to 140° F)
Operating Humidity 5 to 95% noncondensing
Certification (when product or
packaging is marked)
CSA certified
UL listed
CE marked for all applicable directives
Display Type 2 x 16 LCD
Keypad 30 Rubber/carbon Based Keys