Specifications

9
Publication
17472.30 February 1996
Specifications
The following table provides general specifications for the fixed controller.
Description Specification
Program Memory 1K Instruction
Standard RAM
Capacitor - 2 weeks
Lithium Battery - 5 years
Memory Backup Options EEPROM or UVPROM
Typical Scan Time 8 ms/K
Holdup Time (Load Dependent) 20 ms to 700 ms
LED Indicators
RUN, CPU FAULT, FORCED I/O,
BATTERY LOW
Programming
Advanced Programming Software, SLC 500 A.I.
Series programming software, or the HandHeld
Terminal
Power Requirement (max.) 50 VA
Noise Immunity NEMA Standard ICS 2230
Fuse Protection
120/240V ac
24V dc
1.25A
1.6A
Vibration (operating)
Displacement: .015 inch, peaktopeak @
5  57 Hz
Vibration (operating)
Acceleration: 2.5Gs at 57 - 2000 Hz
Duration: 1 hr per axis (x,y,z)
Shock (operating) 30Gs
Environmental conditions
Operating temperature
0
° C to +60° C (+32° F to +140° F )
Storage temperature
-40
° C to +85° C (-40° F to +185° F)
Humidity rating 5 to 95% (noncondensing)
Wire Size 24 AWG to 14 (max.)
Communication DH485 receive
Certification (when product or packaging is
marked)
CSA certified
UL listed
1747L511 only - The capacitor backup is rated at 35° C
(95
° F).
Lithium
battery is optional for the L51
1; standard for the L514.