Installation Guide
PG 4 
The Tee Support can hold a maximum of 50 feet of AllFuel HST Chimney. The 
required parts and general configuration are as shown in Figures 21 and 22. 
CHIMNEY PLACEMENT 
When deciding the location of your chimney, try to avoid modifications to roof beams, 
trusses, wall studs, and other structural components of the building. 
CHIMNEY ENCLOSURE REQUIREMENTS 
Passing Through Rooms: Interior chimneys shall be enclosed where they extend 
through closets, storage areas, occupied spaces, or any place where the surface of the 
chimney could be contacted by persons or combustible materials. The space between 
the outer wall of the chimney and the enclosure shall be at least 2 inches (Fig 2). 
Multi-Story Installations: Consult local building codes for 
requirements in your area. In the U.S., the National Fire 
Protection Association Standard #211 states: “Factory-built 
chimneys that pass through floors of buildings requiring the 
protection of vertical openings shall be enclosed with 
approved walls having a fire resistance rating of not less than 
one hour when such chimneys are located in a building less 
than 4 stories in height, and not less than 2 hours when such 
chimneys are located in a building more than 4 stories in 
height.” In Canada, except in single-family and two family 
dwellings, chimneys which extend through another story must 
have an enclosure with a fire resistance rating equal to or 
greater than that of the floor or roof assembly through which 
they pass. 
AllFuel HST Inc    www.allfuelhst.com  Toll Free: (833) 326-8368 










