Tumble Dryer Installation/Operation Maintenance Manual

© Copyright, Alliance Laundry Systems LLC DO NOT COPY or TRANSMIT
M414545
35
ELECTRICAL REQUIREMENTS
For 31.5" wide Tumblers
NOTE: Minimum wire sizes are obtained from Canadian Electrical Code and are intended for use as a guideline
only. Electrical connections should be made only by a qualified electrical contractor in accordance with all
applicable local and national requirements.
NOTE: DO NOT use aluminum wire.
* Current Ratings vary slightly depending on model, see nameplate.
Table 7
Heat Source Serial Plate Voltage
Terminal Block
Connections Required
Rated
Current
Breaker
Rating
Breaker
Poles
Recommended
Wire Size
Steam CSL 120V/60Hz/1ph L1, Neutral and ground * 20 Amps 1 12 AWG
Gas & CSH 120V/60Hz/1ph L1, Neutral and ground * 15 Amps 1 14 AWG
Gas & Steam 208 or 240V/60Hz/1ph L1, L2 and ground * 15 Amps 2 14 AWG
Gas & Steam 230-240V/50Hz/1ph L1, Neutral and ground * 15 Amps 1 14 AWG
Gas & Steam 208 or 240V/60Hz/3ph L1, L2, L3, and ground * 15 Amps 3 14 AWG
Gas & Steam 380 or 415V/50Hz/3ph L1, L2, L3, and ground * 15 Amps 3 14 AWG
Gas & Steam 460-480V/60Hz/3ph L1, L2, L3, and ground * 15 Amps 3 14 AWG
Electric 208V/60Hz/1ph L1, L2, and ground 104 Amps 125 Amps 2 0 AWG
Electric 240V/60Hz/1ph L1, L2, and ground 92 Amps 100 Amps 2 2 AWG
Electric 240V/50Hz/1ph L1, Neutral and ground 90 Amps 100 Amps 1 2 AWG
Electric 208V/60Hz/3ph L1, L2, L3, and ground 62 Amps 70 Amps 3 4 AWG
Electric 240V/60Hz/3ph L1, L2, L3, and ground 55 Amps 60 Amps 3 4 AWG
Electric 240V/50Hz/3ph L1, L2, L3, and ground 53 Amps 60 Amps 3 4 AWG
Electric 380V/50Hz/3ph L1, L2, L3, and ground 33 Amps 40 Amps 3 8 AWG
Electric 415V/60Hz/3ph L1, L2, L3, and ground 30 Amps 35 Amps 3 8 AWG
Electric 480V/60Hz/3ph L1, L2, L3, and ground 28 Amps 35 Amps 3 8 AWG