Service manual
SC Series Boilers – Installation and Service Manual 
13 
Super Hot SC series boilers are designed for use in closed loop systems and are not intended for open 
systems, as in heating pool water or systems where water is constantly replenished. Operating the boiler 
in an open system will result in premature failure of the heat exchanger. Super Hot boilers may be used 
to heat water in open systems indirectly by installing a heat exchanger, such as the Super Hot C-Coil, to 
separate open and closed systems. 
Heating systems with low temperature return water may cause flue gas moisture to condense on the 
boiler heat transfer surfaces, causing corrosion and restricting flue gas flow. Also, low temperature return 
water may overcool the flue gases, resulting in reduced vent suction. These are natural phenomena and 
are independent of the boiler design. As a guide to avoiding such corrosion and draft problems, it is 
imperative that the return water be not less than 135°F (57°C). 
THE BOILERS MUST ALWAYS BE USED WITH FORCED SYSTEM CIRCULATION. 
2.10  PRESSURE RELIEF VALVE 
A pressure relief valve is supplied as standard equipment. The 
pressure relief valve is extra protection against damage that could 
be caused by malfunctioning controls or excessive water pressure.  
If a pressure relief valve is not used, the warranty is void. 
The pressure relief valve should be installed on the boiler outlet 
with its spindle vertical. The connection between the boiler and the 
relief valve must have at least the area of the valve inlet. 
A discharge pipe should be used. The discharge pipe outlet should 
be positioned over a suitable drain and so arranged that there will 
be no danger of being scalded. The discharge pipe must pitch 
down from the valve and should be no smaller than the outlet of the 
valve. The end of the discharge pipe should not be concealed or 
threaded and should be protected from freezing. Extensive runs, 
traps or bends could reduce the capacity of the pressure relief 
valve. 
No valve of any type should be installed between the pressure relief valve and unit or in the discharge 
pipe. The pressure relief valve is a code requirement. Field installation of the relief valve must be 
consistent with the ANSI/ASME Boiler and Pressure Vessel Code, Section IV. 
Avoid contact with the hot water discharged to prevent personal injury. 
2.11 ELECTRICAL WIRING 
All electrical wiring must conform to the requirements in Section 2.2. 
Run a separate circuit from the electrical service panel through a fused disconnect switch to the boiler. 
This boiler must be electrically bonded to ground in accordance with the requirements of the authority 
having jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA 
70 (current edition) and and/or the Canadian Electrical Code, CSA C22.1 Part 1 (current edition). Field 
wiring shall conform to Section 2.2 and to the temperature limitations of Type T [63°F (35°C) rise] or 
better. 
Make connections as shown in the wiring diagrams provided. For details of electrical wiring for different 
ignition controls, refer to wiring diagrams included in this manual on page 29 to 31. 










