SC Series Boilers – Installation and Service Manual 
14 
Startup Instructions  Section 3 
3.1 PRE-STARTUP 
a.  Fill entire heating system with water and vent or purge air from system. Add water as needed to 
reach boiler operating pressure. Water should be of suitable quality. Do not use water with high 
hardness. 
b.  Check that the venting condensate drain trap is filled with water. 
c.  Check that the tubes tightly and correctly connect the air pressure switches with air chamber. 
d.  Check for and repair any leaks in water piping. 
e.  Check for proper installation of pressure relief valve and venting. 
f.  Check that the electrical wiring matches the wiring diagram in this manual or on the boiler. 
g.  Use a soap solution to check for leaks in gas piping from meter to gas manifold. Repair and retest 
any leaks found. 
h.  Operate circulating pump and vent all radiation units and high points in system piping. 
3.2 STARTUP 
WARNING 
The following instructions are intended as a guide for qualified persons. Before lighting the 
boiler, the pre-startup instructions of Section 3.1 MUST be performed. If you do not follow these 
instructions exactly, a fire or explosion may result causing property damage, personal injury or 
loss of life.
WARNING 
Should boiler overheat, or the gas supply fail to shut off, do not turn off or disconnect the 
electrical supply to the boiler or circulating pump. Instead, shut off the gas supply at a location 
external to the boiler.
a.  Direct Spark Ignition Or Hot Surface Ignition 
This boiler does not have a pilot flame. It is equipped with a direct ignition device which automatically 
lights the main burner. Do not try to light the main burner by hand. 
In the event of failure of any component, either the system will not operate or it will go into safety lockout. 
1)  Make sure the Gas Valve and all electrical power to the boiler are "OFF". 
2)  Set room thermostat to the lowest setting. 
3)  Connect a manometer at pressure tapping on downstream section of gas valve. 
4)  Wait five minutes to clear out any gas. If you smell gas, STOP! Follow the safety instructions 
provided in Section 1.1 under WHAT TO DO IF YOU SMELL GAS. Remember that propane does 
not vent upward naturally. 
5)  Check the ignition control as follows: 
a)  Set room thermostat above room temperature to call for heat and turn power on for the boiler. 
b)  Watch/listen for spark or watch for hot surface to glow bright in the combustion chamber from 
the inspection hole in the front of boiler after 30 seconds pre-purge. If no flame is detected 
within 4 seconds, two or three retries will automatically occur after a 30 second inter-purge. If 
no flame is detected after three or four tries for ignition, all models will automatically lockout 
and restart the ignition sequence after one hour, or after the power is reset. However, if the 
lockout is caused by a blockage of the heat exchanger, venting or air inlet pipe, the controller 