Service manual
SC Series Boilers – Installation and Service Manual 
22 
Adjustments to the input rate can be made by varying the manifold pressure. Normally it should be 
adjusted no more than 0.1 inch w.c. for natural gas or 0.4 inch w.c. for propane from the manifold 
pressure specified on the rating plate for that altitude application. 
WARNING 
Exceeding the allowable input rate can produce dangerous concentrations of carbon monoxide, 
and cause the boiler to overheat resulting in severe personal injury, death or substantial 
property damage. Carbon monoxide is a lethal, colorless and odorless gas.
Input Rate Test
Consult gas company to determine the heating value of the gas supplied in Btu per cubic foot. Operate 
boiler for 15 minutes starting with all parts at room temperature and check input by clocking gas meter 
with all other gas appliances turned off, including their pilot flames. Use the following formula: 
INPUT (Btu/h) = 
Clocked Seconds
Timed) FeetCubic  of (Number x Gas) of  Value(Heating(3600) ×
To ensure accuracy for rating, clock enough cubic feet of gas so that there is at least one revolution of the 
test dial and the clocked time is at least 60 seconds. 
3.8  CHECK OF CONTROLS 
After the unit has been operated for a while, lower the aquastat setting below the setpoint or actual boiler 
water temperature and burner should shut off. Rotate the aquastat higher than setpoint and the main 
burner should ignite. Return the aquastat to its original setpoint and make sure boiler cycles normally.  
Repeat this type of check on the safety high-limit aquastat, thermostat and other system controls to 
ensure all work satisfactorily. If any of the safety or controls do not function, necessary corrections 
should be made immediately. 
3.9  CHECK FOR GAS LEAKS 
To identify gas leaks, smell for gas around boiler area and gas piping connections (See Section 1.1). To 
check a specific area, including the manifold joint connected to the gas valve, for leakage, spray a 
mixture of soap and water onto the suspected area – active bubbling indicates a gas leak. The gas leaks 
of the manifold joint connected to the gas valve outlet should be checked when the boiler is on. DO NOT 
TEST FOR LEAKS WITH AN OPEN FLAME. Gas leaks must be repaired immediately. 
3.10 CHECK THE CONDENSATE DRAIN TUBE 
Check that the tube loop is approximately 4" diameter. The water should fill the loop to form a liquid-filled 
trap and not be plugged with excessive sediment. 