Service manual
SC Series Boilers – Installation and Service Manual 
34 
Troubleshooting Guide  Section 8
8.1 Possible Causes and Solutions 
Problem Possible Cause  Solution 
•  No 
p
ower. 
•
Check 
p
ower switches and wirin
g
.
•  No gas supply to boiler.  •  Check gas source and pressure. 
•  Gas supply pipes are not purged of air.  •  Purge gas line. 
•  No heat demand. 
•  Check if thermostat setting is above room 
temperature and aquastat setting is above 
boiler water temperature. 
•  Flow switch or low water cut off. 
•  Check pump capacity & flow direction. 
Check for correct water levels and air locks. 
•  Gas valve failure (closed position).  •  Check gas valve and replace if necessary. 
•  Faulty wiring. 
•  Check wiring of aquastats, zone valves, and 
thermostats for loose or broken wires and 
repair. 
•  Fault
y
 a
q
uastat, thermostat, or zone valve.
•
Check and re
p
lace if necessar
y
.
•  Pressure switch failure or airflow blockage 
in heat exchanger, venting, air inlet pipe or 
termination. 
•  Check pressure switch and replace if 
necessary. Remove airflow blockages. 
Boiler will not fire. 
•  Fault
y
 controller or control wirin
g
.
•
See "Control trouble troubleshootin
g
".
•  Poor flow in boiler or circulator failure. 
•  Check pump for proper capacity & flow 
direction. Replace if necessary. 
•  Thermostat, heat anticipator, or aquastat 
set too low. 
•  Check and adjust. 
•  Boiler oversized or insufficient radiation.  •  Check and adjust if necessary. 
Boiler goes on and off at 
frequent intervals. 
•  Wrong type of thermostat or controller.  •  Check and replace if necessary. 
•  Gas valve failure 
(
o
p
en 
p
osition
)
.
•
Check 
g
as valve, re
p
lace if necessar
y
.
•  Faulty wiring. 
•  Check wiring of aquastats, zone valves, and 
thermostats for short circuits or incorrect 
wiring. 
Boiler fires continuously. 
•  Fault
y
 a
q
uastat, zone valve or thermostat.
•
Check and re
p
lace if necessar
y
.
•  Boiler is overheated and safety high limit 
aquastat fails to cut out. 
•  Check aquastats and adjust or replace if 
necessary. 
•  Improper wiring.  •  Check and correct. 
•  Foreign matter in heat exchanger.  •  Flush heat exchanger if necessary. 
•  Poor circulation.  •  Check pump for correct flow. 
Rumbling and moaning 
sound in boiler. 
•  Air trapped in heating system.  •  Purge air. 
•  Flue leakin
g
. 
•
Check ventin
g
 and boiler if leakin
g
.
•  Insufficient combustion air to boiler. 
•  Check combustion and ventilation air 
opening in boiler room meets installation 
code requirements, and air differential 
pressure if too low. 
Gas odor. 
•  Leak in gas system. 
•  See “What to do if you smell gas” on cover. 
Have gas fitter test system and repair leaks. 
•  Burner cracked or eroded
•
Check & re
p
lace if necessar
y
. 
•  Not enough combustion air or wrong air 
switch setting 
•  Adjust air shutter & check air switch 
condition 
Flame flash back 
•  The vent or air inlet blocked  •  Check & clean 










