SC Series Boilers – Installation and Service Manual 
9 
Gas service meters:
 The vent terminal requires a clearance of 3 feet (0.9 m) and the air intake a 
clearance of 10 feet (3.0 m) from any gas service regulator vent outlet. Vents are prohibited above the 
gas meter assembly (not propane regulator vents) within 3 feet horizontally of the vertical center line of 
the regulator to a vertical distance of 15 feet (4.6 m). 
The bottom of the vent terminal and the air intake shall be located at least 12 inches above grade plus 
height of the normal snow line. 
Maintain a minimum clearance of 4 feet (1.2 m) below, 4 feet (1.2 m) horizontally from, or 1 foot (300 mm) 
above any door, window, or gravity air inlet into any building. 
A 4 feet (1.2 m) horizontal clearance should be maintained from electric meters, gas meters, regulators 
and relief equipment and in no case above or below, unless a 4’ horizontal distance is maintained. 
The terminal shall not be less than 7 feet above grade where located adjacent to a public walkway and 
shall not terminate over public walkways or over an area where condensate or vapor could create a 
nuisance of hazard or could be detrimental to the operation of regulators, relief valves, or other 
equipment. 
Equivalent Vent/Air Intake Pipe Length and Diameter
In order for the boiler to operate properly, the venting system, including air intake piping (if used), exhaust 
vent piping and terminations, must not be excessively restrictive. Use Table 1 to find exhaust vent and air 
intake pipe maximum and minimum equivalent length for a specified boiler model. The installation must 
be designed so that exhaust vent equivalent length is within the Max. and Min. range of “Exhaust Vent 
Equivalent Length”. Similarly, Air Intake Pipe must be within the Max. and Min. range of “Air Intake Pipe 
Equivalent Length”. Use the notes in Table 1 to calculate the equivalent length in feet for exhaust vent 
and air intake pipe. 
Table 1. Equivalent Length of Venting System 
Exhaust Vent 
Equivalent Length in Feet 
Air Intake Pipe 
Equivalent Length in Feet 
3 inch diameter  4 inch diameter  3 inch diameter  4 inch diameter 
MODEL 
Min. Max. Min. Max. Min. Max. Min. Max. 
SC-35  8  40      0  45     
SC-70 8 40      0 45     
SC-105  8  40      0  45     
SC-140 8 40      0 45     
SC-175      8  40      0  45 
SC-210  8 40  0 45 
SC-245      8  40      0  45 
SC-280  8 40  0 45 
NOTES: 
1.  Calculate the Equivalent Length by measuring the total centerline length in feet and 
adding 6 feet for each 90-degree elbow used and adding 3 feet for each 45-degree 
elbow used. The calculated Equivalent Length must be within the Max. and Min. limits 
for the specified boiler model. 
2.  The air inlet and exhaust vent must remain 3 inch diameter for SC-35 to SC-140, and 
4 inch diameter for SC-175 to SC-280. 