Chapter 1: Overview
24
The MDI and MDI-X settings do not apply when ports are operating at
1000 Mbps.
Maximum
Distance
The ports have a maximum operating distance of 100 meters (328 feet).
Cable
Requirements
The cable requirements of the ports are given in Table 1.
Note
For the cable requirements for the ports on the AT-x510-28GPX and
AT-x510-52GPX Switches for PoE devices, refer to Table 3 on
page 26.
Port Pinouts Refer to Table 18 on page 87 and Table 19 on page 88 for the port pinouts
of the 10/100/1000Base-T twisted pair ports.
Table 1. Twisted Pair Cable for the 10/100/1000Base-T Ports
Cable Type 10Mbps 100Mbps 1000Mbps
Standard TIA/EIA 568-B-
compliant Category 3 shielded
or unshielded cabling with 100
ohm impedance and a
frequency of 16 MHz.
Yes Yes No
Standard TIA/EIA 568-A-
compliant Category 5 or TIA/
EIA 568-B-compliant Enhanced
Category 5 (Cat 5e) shielded or
unshielded cabling with 100
ohm impedance and a
frequency of 100 MHz.
Yes Yes Yes
Standard TIA/EIA 568-B-
compliant Category 6 or 6a
shielded cabling.
Yes Yes Yes