Specifications
28
We reserve the right to modify technical specifications without prior notice.
UK830301/170306 © Alpha-InnoTec GmbH
Commissioning
Proceed as follows:
Conduct a thorough installation inspection and go
through the items on the general checklist.
“General checklist”.
The installation inspection will prevent damage to
the heat pump system that could be caused by in-
correct installation work.
Make sure of the following:
•
Clockwise rotary eld of the load power
supply (compressor).
•
Installation and assembly of the heat station
according to the information in this operating
manual.
•
All electric installation work must be properly
completed.
•
A 3-pole automatic circuit-breaker must be
installed for the compressor. It must have a con-
tact gap of at least 3 mm.
•
The heating circuit and the heat source must be
rinsed, filled and bled thoroughly.
•
All valves and shut-off devices of the heating cir-
cuit must be open.
•
The concentration of the anti-freeze agent must
be sufficient.
•
All valves and shut-off devices of the heat source
must be open.
•
All pipe systems and components of the system
must be sealed.
Carefully fill out and sign the completion report for
heat pump systems.
“Completion report for heat pump systems”.
In Germany:
Send completion report for heat pump systems to
the manufacturer’s factory customer service de-
partment.
Outside of Germany:
Send completion report for heat pump systems to
the manufacturer’s local partner.
Overview “Customer service”.
The heat pump system will be commissioned by
customer service personnel authorized by the ma-
nufacturer. There is a fee for commissioning!
The initial filling and commissioning of the hot water tank
must be carried out by a qualified technician.
Make sure of the following:
•
The water supply to the hot water tank must be
open.
•
The hot water tank must be filled.
If the heat pump is switched on with an empty
tank, the control element will indicate a malfunc-
tion.
Operating manual of the heating and heat pump re-
gulator.
safety temperature limiter
A safety temperature limiter is built into the electric hea-
ting element. In the event of a malfunction in the heat pump
or air in the system, check whether the reset button of the
safety temperature limiter has tripped. If this is the case,
push in the button.
1 Safety temperature button on
electric heating element
2 Reset button