Instruction manual
Active Alarm or
Abnormal Condition
Probable Causes Corrective Action
Output 1 Tripped
Output 1 hardware protection
mode engaged
(only active with optional PIM
1. Over Current
2. Check Settings
Output 1 Tripped
Output 1 hardware protection
mode engaged
(only active with optional PIM
1. Over Current
2. Check Settings
Charger Failure Alarm
Bad batteries
Inverter Module not seated
Inverter Module failure?
1. Open the Battery Circuit Breaker,
3. If Display drops out….
4. Pull out the Inverter Module
5. Inspect the Inverter Module and rear
Anderson connectors.
6. Re-seat the Inverter Module
7. Turn the Battery Circuit Breaker back
on.
8. Check charging current on display.
9. Run Self Test (press Down and Enter
11. Check Battery physical condition.
returned.
15. Replace Inverter Module
Inverter Disconnected
The Inverter Module is not properly
connected
1. Reseat Inverter Module
2. Check Ribbon Cable
Inverter Temperature
temperature (Standby operations
suspended until temperature drops
1. Check Fan
4.4 Alarm Indications, continued
70
017-805-B0-010 Rev. K