Instruction manual

6.0 Specications
6.1 Intelligent CableUPS North American Models

American models of the Intelligent CableUPS.
Models: XM2-906HP XM2-910 XM2-1350-48 XM2-915 XM2-915HV XM2-922 XM2-922HV XM2-918HP XM2-924HP
Electrical
Input Voltage (Vac): 120/240 120/240 120/240 120/240 120/240 208/240 240 120/240 208/240
Input Voltage Window: -30 to +20% -20 to +15% -20 to +15% -20 to +15% -30 to +15% -20 to +15% -30 to +15% -20 to +15% -20 to +15%
Input Frequency: 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz 60Hz
Input Frequency Window: ±3Hz ±3Hz ±3Hz ±3Hz ±3Hz ±3Hz ±3Hz ±3Hz ±3Hz
Output Voltage (Vac): 63/87 63/75/87 63/75/87 63/75/87 63/75/89 63/75/87 63/75/89 63/75/87 63/75/87
Output Current (A): 8/6 10/10/10 22/15/15 15/15/15 20/17.5/15 22/22/22 22/22/22 22/18/18 22/22/24
Max Output Power (VA): 540 900 1350 1350 1350 2025 2025 1620 2160
Output Waveform: Quasi-square wave
Voltage Regulation
1
: ±5% ±5% ±5% ±5% ±5% ±5% ±5% ±5% ±5%
Output
Frequency
Stability:
Line Mode 60Hz Nominal
Inverter Mode 60Hz, ±0.05%
Short Circuit Protection: <150% of maximum current rating
Transfer Characteristics: Uninterrupted output
Battery Voltage (Vdc): 36 36 48 36 36 48 48 36 48
Efficiency
(Typical Load Range)
Line Mode: 80-87% 86-90% 90-92%
Standby Mode: 79-84% 82-85% 84-86%
Battery Charger
Temperature Compensation: Programmable (0 to 5mV/Cell/°C)
Charger Current: 10A at 80% load and nominal input (bulk charge mode)
Three Stage: Bulk, Accept, Float
Mechanical
Status Display: 2 x 20 Blue LCD with backlight
Dimensions
H x W x D (in/mm):
8.8 x 15 x 13 / 222 x 381 x 330
Approx. Weight (lb/kg): 53/24 62/28.1 70/31.8 70/31.8 72/32.7 92/41.7 96/43.5 72/32.7 95/42.9
Finish: Black, epoxy powdercoat
Environment
Operating Temperature: -40 to 55°C / -40 to 131°F
Relative Humidity: 0 to 95% non-condensing
Agency Compliance: FCC Part 15 Class A, UL1778, UL1012, CSA 22.2 No. 107.1
Optional Features
Standard Protective Interface Module (PIM/N+1): Provides two programmable outputs from a single XM2 CableUPS power supply for redundancy in critical applications. The PIM
protects system components and provides isolation between distribution legs by shutting down the individual load during over-current conditions.
1
Note: Voltage regulation is maintained over both line and load ranges.

83
017-805-B0-010 Rev. K