2.2 Recommended Installation Layout
Verify input (supply) wiring has been run to site in accordance with applicable local and national
electrical codes.
The ACS Series system is heavy equipment. To prevent personal injury or equipment damage, use lifts
and extreme care when handling.
Ventilation and Cooling:
Therectier/chargerisratedtobetterperformwithin18°F(–10°C)and122°F(+50°C)
temperature range.
To calculate the required air displacement (exchange) volume, please use the following equation:
V = BTU x e (0.125 x H x Tk/To) / (Tr -Tk)
Where:
V=Airow:[cubicmeter/hour]
BTU: Total dissipated heat
Tr:Maximumallowedroomtemperature[°K]{i.e.50°C=323°K]
Tk= Temperature of input cooling air
To=273°KH=Altitude[km]
For adequate ventilation and safe access, verify the following minimum clearances around the charger:
3 in. (10 cm) on the sides and top of the unit.
7 in. (18 cm) in back of the unit.
3 feet (1 meter) in front of the unit.
Shouldseismicconditionsrequireamoresecureinstallationtheunitmaybeboltedtotheoor.
Four (4) holes are provided for this purpose.
23.6”/600mm
21.1”/536mm
24.6”/625mm 23”/584mm
Fig. 2-1, Cabinet Footprint with dimensions