User Manual

745-680-C0-002, Rev.B
16
3.3 AlphaCell
TM
Battery Maintenance Log
Follow this sample when lling out the maintenance log (following page).
Evaluation Procedure
#1
Evaluation Procedure
#2
Evaluation Procedure
#3
Vdc
Float
No
Load
Conductance
mhos @
77°F
Vdc 24
Hour
OCV
Conductance
mhos @
77°F/25°C
Vdc @
100A after
10 seconds
Vdc 24
Hour
OCV
A 1 195GXL 4/08 3/08 .2 70° 13.4 1100
A 2 195GXL 4/08 3/08 .2 70° 13.5 1080
A 3 195GXL 4/08 3/08 .2 70° 13.4 1120
B 1 195GXL 4/08 3/08 .1 70° 13.4 1090
B 2 195GXL 4/08 3/08 .1 70° 13.4 1105
B 3 195GXL 4/08 3/08 .1 70° 13.6 1060
A 1 195GXL 4/08 3/08 7/8 .1 85° 13.3 1120
A 2 195GXL 3/08 7/8 .1 85° 13.3 1100
A 3 195GXL 3/08 7/8 .1 85° 13.4 1105
B 1 195GXL 3/08 7/8 .1 85° 13.2. 1070
B 2 195GXL 3/08 7/8 .1 85° 13.2 1100
B 3 195GXL 3/08 7/8 .1 85° 13.2 1080
String
Battery Type
Battery
Initial Install Date
Mfr. Date Code
PM Date
Float Current
Battery Temp
Node / Location
Power Supply Type
Load (kW)