Manual

042-288-B0-001, Rev. A
77
Fig. 7-1, Captive Fastener Location, CE-3x2 5K-T
7.0 Maintenance, continued
7.2 Filter Cleaning, CE-3x2 5K-T
The air intake lter (Alpha P/N 561-216-10) is located on the rear door of the enclosure.
Failure to keep the lter clean, or using improperly installed lters, may cause system failure due
to dirt buildup or lack of cooling air. Equipment failures caused by lter blockage, incorrect lter
substitution, or dirt ingress due to clogged or improperly installed lters are not covered under
warranty.
CAUTION!
Filter Removal, Replacement, and Cleaning
1. Unlock and remove the rear door.
2. Pull the four captive fasteners out, Fig. 7-1.
3. Tilt the lter frame away from the door and remove the lter, Fig. 7-2.
4. Clean the lter using a vacuum or compressed air (if available) to remove loose dust and
dirt. Then use a soap and water solution to remove any trapped dirt. Use compressed
air to dry the lter. After cleaning, re-coat the lters using RP Super Filter Coat Adhesive,
available from local suppliers.
5. Replace the lter (Verify the “Air Flow” indicating mark faces into the enclosure) and
refasten the lter frame.
6. Replace and lock the rear door.
Fig. 7-2, Air Filter Removal, CE-3x2 5K-T