746-257-B2-001, Rev. B (01/2014)
10.1 Denitions and Settings
10.0 Alpha MIB Parameters
Parameter OID Description Access Type Value
GENERAL CONTROLS
atiMgmtSysTamperPolarity 1.3.6.1.4.1.926.1.3.2.6.1.0 Determines when tamper is active Read/Write Integer 1=doorOpenWhenContactOpen
2=doorOpenWhenContactClosed
(default)
atiMgmtSysAlphaBusSize 1.3.6.1.4.1.926.1.3.2.6.2.0 Internal microprocessor communications
bus size. Alpha XM2 series power supplies
use 9 bit. Alpha GMX and VMX series
supplies use 8 bit
Read/Write Integer 1=9 Bit (Default)
2=8 Bit
atiMgmtSysGnrlInfoCongs 1.3.6.1.4.1.926.1.3.2.7.1 Object Identier
atiMgmtSysGnrlInfoCongsMain 1.3.6.1.4.1.926.1.3.2.7.1.1.0 An ASCII string programmed into the main
board non-volatile memory.
Read Only Octet String Product number, conguration
number serial number, etc.
atiMgmtSysGnrlInfoCongsDaughter 1.3.6.1.4.1.926.1.3.2.7.1.2.0 An ASCII string programmed into the C/D
battery circuitry.
Read Only Octet String Product number, conguration
number serial number, etc.
atiMgmtSysGnrlInfoCongsBase 1.3.6.1.4.1.926.1.3.2.7.1.3.0 An ASCII string describing the base
conguration of the device.
Read Only Octet String i.e. DSM3, DSM3x, DPM, etc.
ENVIRONMENTAL I/O CONTROLLER
atiMgmtSysIo 1.3.6.1.4.1.926.1.3.2.8 Object Identier
atiMgmtSysIoSelect 1.3.6.1.4.1.926.1.3.2.8.1 Indicates what function the IO pins are
being used for
Read/Write Integer 1 = Generic
2 = lapOnly
3 = heaterControlOnly
4 = generatorOnly
5 = heaterControlAndLap
6 = generatorAndLap
atiMgmtSysIoLAPState 1.3.6.1.4.1.926.1.3.2.8.2 Current state of the LAP device Read Only Integer 1: notInstalled(1)
2: ok(2)
3: acNotPresent(3)
4: lapBlown(4)
5: lapFail(5)
atiMgmtSysIoGenState 1.3.6.1.4.1.926.1.3.2.8.3 State of the DC Emergency Generator
when sense lines are used
Read Only Integer 1: notInstalled(1)
2: genOff(2)
3: genRunning(3)
4: genNotDetected(4)
5: error(5)
atiMgmtSysIoPinCtrl 1.3.6.1.4.1.926.1.3.2.8.20 Status of the ENV connector Output Pin
(Pin 3)
Read Only Integer 1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn4 1.3.6.1.4.1.926.1.3.2.8.21 Status of the ENV connector Input Pin#4 Read Only Integer 1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn5 1.3.6.1.4.1.926.1.3.2.8.22 Status of the ENV connector Input Pin#5 Read Only Integer 1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn6 1.3.6.1.4.1.926.1.3.2.8.23 Status of the ENV connector Input Pin#6 Read Only Integer 1 = Contact Open
2 = Contact Closed
PLATFORMS
atiProductPlatforms 1.3.6.1.4.1.926.1.4 Object Identier
atiBroadbandUPS 1.3.6.1.4.1.926.1.4.1 Object Identier
atiBBSysView 1.3.6.1.4.1.926.1.4.1.1 Object Identier
atiBBSysViewSelects 1.3.6.1.4.1.926.1.4.1.1.1 Object Identier
atiBBSysViewSelfTestControl 1.3.6.1.4.1.926.1.4.1.1.1.1.0 Starts/Stops a system self-test. Read/Write Integer 1=Stop
2=Start
atiBBSysViewSelfTestInhibit 1.3.6.1.4.1.926.1.4.1.1.1.2.0 System self-test is prevented. On reset,
the IDH4 gets this value from the master
XM2 (in a system with more than one
power supply).
Read/Write Integer 1=Normal (Default)
2=Inhibited
atiBBSysViewSystemControlMgr 1.3.6.1.4.1.926.1.4.1.1.1.3.0 If the System Control Manager is running,
the Small System Controller/Administrator
(SSC or SSA) is running and there is
coordination between the power supplies
for charging, testing, etc. The value of this
item is stored in non-volatile memory.
Read/Write Integer 1=Running
2=Disabled