10.1 Denitions and Settings
10.0 Alpha MIB Parameters
Parameter OID Description Access Type Value
GENERAL CONTROLS
atiMgmtSysTamperPolarity 1.3.6.1.4.1.926.1.3.2.6.1.0 Determines when tamper is active Read/Write Integer 1=doorOpenWhenContactOpen
2=doorOpenWhenContactClosed
(default)
atiMgmtSysAlphaBusSize 1.3.6.1.4.1.926.1.3.2.6.2.0 Internal microprocessor communications
bus size. Alpha XM2 series power supplies
use 9 bit. Alpha GMX and VMX series
supplies use 8 bit
Read/Write Integer 1=9 Bit (Default)
2=8 Bit
atiMgmtSysGnrlInfoCongs 1.3.6.1.4.1.926.1.3.2.7.1 Object Identier
atiMgmtSysGnrlInfoCongsMain 1.3.6.1.4.1.926.1.3.2.7.1.1.0 An ASCII string programmed into the main
board non-volatile memory.
Read Only Octet String Product number, conguration
number serial number, etc.
atiMgmtSysGnrlInfoCongsDaughter 1.3.6.1.4.1.926.1.3.2.7.1.2.0 An ASCII string programmed into the C/D
battery circuitry.
Read Only Octet String Product number, conguration
number serial number, etc.
atiMgmtSysGnrlInfoCongsBase 1.3.6.1.4.1.926.1.3.2.7.1.3.0 An ASCII string describing the base
conguration of the device.
Read Only Octet String i.e. DSM3, DSM3x, DPM, etc.
ENVIRONMENTAL I/O CONTROLLER
atiMgmtSysIo 1.3.6.1.4.1.926.1.3.2.8 Object Identier
atiMgmtSysIoSelect 1.3.6.1.4.1.926.1.3.2.8.1 Indicates what function the IO pins are
being used for
Read/Write Integer 1 = Generic
2 = lapOnly
3 = heaterControlOnly
4 = generatorOnly
5 = heaterControlAndLap
6 = generatorAndLap
atiMgmtSysIoLAPState 1.3.6.1.4.1.926.1.3.2.8.2 Current state of the LAP device Read Only Integer 1: notInstalled(1)
2: ok(2)
3: acNotPresent(3)
4: lapBlown(4)
5: lapFail(5)
atiMgmtSysIoGenState 1.3.6.1.4.1.926.1.3.2.8.3 State of the DC Emergency Generator
when sense lines are used
Read Only Integer 1: notInstalled(1)
2: genOff(2)
3: genRunning(3)
4: genNotDetected(4)
5: error(5)
atiMgmtSysIoPinCtrl 1.3.6.1.4.1.926.1.3.2.8.20 Status of the ENV connector Output Pin
(Pin 3)
Read Only Integer 1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn4 1.3.6.1.4.1.926.1.3.2.8.21 Status of the ENV connector Input Pin#4 Read Only Integer 1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn5 1.3.6.1.4.1.926.1.3.2.8.22 Status of the ENV connector Input Pin#5 Read Only Integer 1 = Contact Open
2 = Contact Closed
atiMgmtSysIoPinIn6 1.3.6.1.4.1.926.1.3.2.8.23 Status of the ENV connector Input Pin#6 Read Only Integer 1 = Contact Open
2 = Contact Closed
PLATFORMS
atiProductPlatforms 1.3.6.1.4.1.926.1.4 Object Identier
atiBroadbandUPS 1.3.6.1.4.1.926.1.4.1 Object Identier
atiBBSysView 1.3.6.1.4.1.926.1.4.1.1 Object Identier
atiBBSysViewSelects 1.3.6.1.4.1.926.1.4.1.1.1 Object Identier
atiBBSysViewSelfTestControl 1.3.6.1.4.1.926.1.4.1.1.1.1.0 Starts/Stops a system self-test. Read/Write Integer 1=Stop
2=Start
atiBBSysViewSelfTestInhibit 1.3.6.1.4.1.926.1.4.1.1.1.2.0 System self-test is prevented. On reset,
the IDH4 gets this value from the master
XM2 (in a system with more than one
power supply).
Read/Write Integer 1=Normal (Default)
2=Inhibited
atiBBSysViewSystemControlMgr 1.3.6.1.4.1.926.1.4.1.1.1.3.0 If the System Control Manager is running,
the Small System Controller/Administrator
(SSC or SSA) is running and there is
coordination between the power supplies
for charging, testing, etc. The value of this
item is stored in non-volatile memory.
Read/Write Integer 1=Running
2=Disabled