Instruction Manual

Doc. #: 0260011-J0 Rev B
16
Table B Pinouts for 40 Pin Connector Interface to CXCR
1 DIN1 2 DIN2 Output circuit breaker CB5
3 D_COM Fused DC- 4 DIN3 MBS
5 DIN4 6 DIN5 Input circuit breaker CB6
7 D_COM Fused DC- 8 DIN6 TVSS
Not Used
9 N/A 10 N/A
11 N/A 12 N/A
Analog Inputs
13 V1+ 14 T1+
Battery temperature probe
(Figure 6)
15 V1- 16 T1-
17 I1+ 18 T2+
Battery temperature probe
(Figure 6)
19 I1- 20 T2-
Relay Contacts (rated at 60VDC or 42V AC, 0.5A)
From the factory, the Cordex controller is congured with the relay assignments shown below. The relays can
be unassigned from their factory conguration and remapped. For example Relay 2, K2, can be unassigned
from LVD #2 then remapped as an alarm relay. Refer to the Cordex controller manual for details.
21 K1_NO
LVD #1
22 K2_NO
LVD #223 K1_NC 24 K2_NC
25 K1_COM 26 K2_COM
27 K3_NO
LVD #3
28 K4_NO
Power System Minor alarm29 K3_NC 30 K4_NC
31 K3_COM 32 K4_COM
33 Not installed 34 Not installed
35 K5_NO
Power System
Major alarm
36 K6_NO
AC Mains High/Low alarm37 K5_NC 38 K6_NC
39 K5_COM 40 K6_COM
2.4  Low Voltage Battery Disconnect (Optional)
A built-in AMPS24 shutdown cuts off the load
during a lengthy power outage.
Installing an LVD (Alpha part number 020-
615-20), between the AMPS24 HP and the
batteries, disconnects the AMPS24 HP from
the batteries to prevent further drain of the
batteries during a lengthy power outage.
The controller is configured with a relay
assigned to LVD #1. Figure 5 shows how to
wire the normally closed contacts of the LVD
#1 relay to activate the LVD. The activation
value is set in the Controls >LVD C ontrol
menusee the controller software manual.
AMPS24 HP
LVD
LVD#1
K1 Relay
Pin 25
Pin 23
Pin 21
Batteries
-48V@Pin 3
Figure 5 LVD wiring
Pinouts available at the AMPS24 40 pin connector
– see Figure 4 and (Table B.