96
;290; ;DC 4 : Vdc_in Low Start; ;49; ;V;
;291; ;DC 4 : Vdc_in Low Transfer; ;42; ;V;
;292; ;DC 4 : Vdc_in Low Stop; ;42; ;V;
;293; ;DC 4 : Vdc_in High Start; ;58; ;V;
;294; ;DC 4 : Vdc_in High Transfer; ;61; ;V;
;295; ;DC 4 : Vdc_in High Stop; ;61; ;V;
x The same as Group DC 1
;300; ;DC 5 : Vdc_in Low Start; ;49; ;V;
;301; ;DC 5 : Vdc_in Low Transfer; ;42; ;V;
;302; ;DC 5 : Vdc_in Low Stop; ;42; ;V;
;303; ;DC 5 : Vdc_in High Start; ;58; ;V;
;304; ;DC 5 : Vdc_in High Transfer; ;61; ;V;
;305; ;DC 5 : Vdc_in High Stop; ;61; ;V;
x The same as Group DC 1
Synchronization with ACin source
;370; ;AC : Fac_in Low Start; ; 57.3; ;Hz;
x Below this value and above parameter 371, the inverters will try to synchronize with the
ACin frequency
;371; ;AC : Fac_in Low Stop; ;57.0; ;Hz;
x Below this value the inverters will stop trying to synchronize with the ACin frequency
;372; ;AC : Fac_in High Start; ;62.7; ;Hz;
x Above this value and less than parameter 375, the inverters will try to synchronize with the
ACin frequency
;375; ;AC : Fac_in High Stop; ;63; ;Hz;
x Above this value, the inverters will trying stop to synchronize with ACin
Parameters for AC Groups
;380; ;AC 1 : Vac_in Low Start; ;91.5; ;V;
x ACin Voltage where a higher value causes the converter AC/AC to start
x Range: 83 to 143, default: 91.5 V