Instruction Manual

97
Doc. #: 0260011-J0 Rev B
;381; ;AC 1 : Vac_in Low Transfer; ;81.5; ;V;
x ACin Voltage where a lower value transfers the load from the AC/AC converter to the DC/
AC converter
x Range: 80 to 143, default: 81.5 V
;382; ;AC 1 : Vac_in Low Stop; ; 81.5; ;V;
x ACin Voltage where a lower value causes the AC/AC converter to stop
x It is possible to step down to 150 Vac. In this case, the AC/DC converter runs at a lower
power. The DC/DC converter supplies the rest (ONLY if DC is available, if not, there is a
derating)
;383; ;AC 1 : Vac_in High Start; ; 140; ;V;
x ACin Voltage where a lower value causes the AC/AC converter to re-start
;384; ;AC 1 : Vac_in High Transfer; ;143; ;V;
x ACin Voltage where a higher value transfers the load of the charge from the converter AC/
AC to the DC/AC converter
;385; ;AC 1 : Vac_in High Stop; ;143; ;V;
x ACin Voltage where a higher value causes the AC/AC converter to stop
;390; ;AC 2 : Vac_in Low Start; ;91.5 ;V;
;391; ;AC 2 : Vac_in Low Transfer; ;81.5; ;V;
;392; ;AC 2 : Vac_in Low Stop; ;81.5; ;V;
;393; ;AC 2 : Vac_in High Start; ;140; ;V;
;394; ;AC 2 : Vac_in High Transfer; ;143; ;V;
;395; ;AC 2 : Vac_in High Stop; ;143; ;V;
x The same for Group AC 1
;400; ;AC 3 : Vac_in Low Start; ;91.5 ;V;
;401; ;AC 3 : Vac_in Low Transfer; ;81.5; ;V;
;402; ;AC 3 : Vac_in Low Stop; ;81.5; ;V;
;403; ;AC 3 : Vac_in High Start; ;140; ;V;
;404; ;AC 3 : Vac_in High Transfer; ;143; ;V;
;405; ;AC 3 : Vac_in High Stop; ;143; ;V;
x The same for Group AC 1