7. Maintenance
7.1 Preventive Maintenance
This equipment requires regular maintenance. The maintenance must be done by qualified service personnel
only. Contact Alpha Technologies at 1-888-462-7487 for any assistance with maintenance.
7.2 Recommended maintenance schedule
Task: Interval
Clean ventilation openings 1-6 month
Inspect all cable connections, re-torque if necessary 1 year
Verify alarm/control settings 1 year
Verify alarm relay operation 1 year
Verify circuit breaker operation 1 year
7.3 Tools, Spare Parts and Equipment
Table I Tools
Required Service /Maintenance Commissioning
Torque wrench X X
#2 Philips screw driver X X
#2 at head screw driver (3/16") width head X
#1 at head screw driver (1/8") width head X
Small at head screw driver (1/16") width head X X
9/16" hex driver X
3/8" hex driver X
7/16" combo wrench X
7/16" at gear ratchet X
9/16" combo wrench X
9/16" at gear ratchet X
11/16" combo wrench X
11/16" at gear ratchet X
6" ratchet extension X
3" ratchet extension X