Table K Alarm Codes
Alarm Type Description Cause Solution
230 REDUND + 1
LOST
Generate alarm code 230
and text "Redundancy + 1
Lost" when condition is true
Lost of inverter redundancy +
1 inverter
Replace defective inverter(s) or
adapt conguration
231 SYS
SATURATED
Generate alarm code 231
and text "Sys Saturated"
when the condition is true
Load of system is greater
than the preset value
Reduce load, or add inverter to
the system or reduce the number
of redundant units in Inverters >
Set Output, or change the alarm
level trigger.
232 MAIN SOURCE
LOST
Generate alarm code 232
and text "Mains source lost"
when the condition is true
Priority source lost (depends
on the conguration AC/AC 
or Online)
1) In AC/AC conguration: 
Reconnect AC IN or check
conguration or check live 
value. 2) In Online conguration: 
Reconnect DC or check
conguration or check level 
voltage
233 SEC SOURCE
LOST
Generate alarm code 233
and "Sec Source Lost"
when the condition is true
Secondary source
lost (depends on the
conguration AC/AC or 
Online)
1) In ONLINE conguration: 
reconnect AC IN or check
conguration or check live value. 
2) In AC/AC conguration: 
reconnect DC or check
conguration or check level 
voltage
234 T2S BUS FAIL Generate alarm code 234
and "T2S Bus Fail" when
the condition is true
The communication bus to
T2S has failed
Hardware problem. Replace T2S
235 T2S FAILURE Generate alarm code 235
and text "T2S Failure" when
the condition is true
T2S has failed Hardware problem. Replace T2S
236 T2S STARTED Write event "T2S Started" in
log le when T2S is started 
(powered up)
T2S has started
237 LOG CLEARED Write event "Log Cleared"
in log le when the log is 
cleared
T2S has cleared the log
238 CONFIG
MODIFIED
Write event "Cong 
Modied" in log le when 
conguration is modied.
Conguration is modied
239 NEW MOD
DETECTED
Write event "New Mod
Detected" in log le when 
new module is seen by T2S
One more module is plugged
240 DATE & TIME
MOD
Write event "Date & Time
Mod" in log le when date 
and/or time are modied
Date and time are modied
241 CFG READ IN
MOD
Write event "Cfg Read In
Mod" in log le when T2S 
had read the conguration 
le from TSI inverter. 
Tipically after insterting new
T2S on live system.
T2S has read the CFG
242 LOG
NEARLY FULL
Generate alarm code 242
and text "Log Nearly full"
when the condition is true
This item will be set as, No
alarm, Minor or major alarm.
(see conguration le)
Clear log le
243 T2S FLASH
ERROR
Flash of T2S is corrupt and
has failed
T2S failure Hardware problem. Replace T2S