Battery Enclosure (BE) installation procedure on UPE Enclosure DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure Electrical Hazards Battery Safety Notes Battery systems represent a risk of electrical shock and high short circuit currents. The following precautions should be observed when maintaining VRLA (Valve-regulated Lead Acid) batteries: 1. 2. 3. 4. 5. 6. 7. 8. Remove all personal metal objects (watches, rings, etc.) Use insulated tools. Wear eye protection and rubber gloves. Observe circuit polarities. Do not make or break live circuits.
Battery Enclosure (BE) installation procedure on UPE Enclosure Parts list: Qty. Description 1 Battery Enclosure (BE) (033-074-20) 1 1 3 1 Y-adapter for battery cabling (p/n 874-655-20) Optional, Y-configured Tamper Switch cable (p/n 874-684-21) VRLA batteries (manufacturer and type to match existing batteries).
Battery Enclosure (BE) installation procedure on UPE Enclosure Unpack the Battery Enclosure (BE) and inspect for damage. DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure Procedure for adding Alpha Technologies Battery Enclosure (BE) to existing UPE enclosures: 1. Begin with a UPE enclosure system which is currently not on-line. CAUTION: The total installed weight of the system is approximately 600 lbs. Verify the stability of the system before loading additional batteries. DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure 2. Remove the front door of the enclosure and set aside (Internal components not shown for clarity). DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure Wing nut location 3. Remove the wing nuts from each of the front corners of the lid of the UPE. Set the lid aside. DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure 4. Install the BE by engaging the retaining channel (see detail below) on the rear lip of the cabinet. Reinstall wing nuts. Detail of retaining channel and cabinet lip. DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure The steps outlined below are referenced in the figure on the following page: 5. Place three new batteries into BE-UPE and connect them with a fused Battery Cable Kit (BCK). 6. Move the Remote Temperature Sensor (RTS) at this time, and secure it to the center of the middle battery on the upper battery shelf. 7.
Battery Enclosure (BE) installation procedure on UPE Enclosure Temperature Sensor (moved from lower battery shelf to corresponding position in upper battery shelf) - - - Step 5 Newly-installed batteries in upper Battery Enclosure (BE) Long Black wire Step 6 Long Red wire Fuse Spacer + + + Wires pass through hole in Battery Enclosure Step 7 or RED + Step 11 R.T.
Battery Enclosure (BE) installation procedure on UPE Enclosure 12. Install original lid on top of BE-UPE. DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure a. b. c. e. d. f. Dual Closed-loop magnetic tamper switch a. b. c. d. e. f. Top enclosure switch. Mounted to side flange with 2 #6-32 screws. Top enclosure magnet. Mount to door studs with 2 #6-32 KEPS nuts. Shelf cutouts may vary. Bottom enclosure magnet. Mount to door studs with 2 #6-32 KEPS nuts. Bottom enclosure switch. Mount to top shelf with 2 #6-32 screws. 2-pin connector, plugs into XM/XMS2 or transponder. DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure 13. Install door on BE-UPE. DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure 14. Replace door on UPE. End of Installation Procedure DOCUMENT NO.
Battery Enclosure (BE) installation procedure on UPE Enclosure 17.0" 28.0" 52.0" 26.0" 15.0" 15. Overall dimensions of completed enclosure assembly DOCUMENT NO.