Table U CXC Modbus PDU address denition for function code 0x03 (read holding registers)
PDU Address
Variable Name Variable Description
Number of
Bytes
0x018A Signal_5_In_Signal_Table_5 Timer 5 4 (signed int_32)
0x018C Signal_6_In_Signal_Table_5 Timer 6 4 (signed int_32)
0x018E Signal_7_In_Signal_Table_5 Timer 7 4 (signed int_32)
0x0190 Signal_8_In_Signal_Table_5 Timer 8 4 (signed int_32)
0x0192 Signal_9_In_Signal_Table_5 Timer 9 4 (signed int_32)
0x0194 Signal_10_In_Signal_Table_5 Timer 10 4 (signed int_32)
0x01C2 Signal_1_In_Signal_Table_6 Counter 1 4 (signed int_32)
0x01C4 Signal_2_In_Signal_Table_6 Counter 2 4 (signed int_32)
0x01C6 Signal_3_In_Signal_Table_6 Counter 3 4 (signed int_32)
0x01C8 Signal_4_In_Signal_Table_6 Counter 4 4 (signed int_32)
0x01CA Signal_5_In_Signal_Table_6 Counter 5 4 (signed int_32)
0x01CC Signal_6_In_Signal_Table_6 Counter 6 4 (signed int_32)
0x01CE Signal_7_In_Signal_Table_6 Counter 7 4 (signed int_32)
0x01D0 Signal_8_In_Signal_Table_6 Counter 8 4 (signed int_32)
0x01D2 Signal_9_In_Signal_Table_6 Counter 9 4 (signed int_32)
0x01D4 Signal_10_In_Signal_Table_6 Counter 10 4 (signed int_32)
Table V CXC Modbus PDU address denition for function code 0x04 (read input registers)
PDU
Address
Variable Name Variable Description
Response
Data
Format
0x0001 Relays_Total (Y) Read number of relays BINARY
0x0002 Total_Active_Alarms (Z) Read total active alarms BINARY
0x0003 System_Major_Alarm Read system major alarm status BINARY
0x0004 System_Minor_Alarm Read system minor alarm status BINARY
0x0011 Alarm_Tables_Total (X) Read number of alarm tables (X<=0x1E) BINARY
0x0012 Alarms_Total_In_Alarm_Table _1 (A1)
Read number of alarm in alarm table 1 (A1
<= 0x3F)
BINARY
0x0013 Alarms_Total_In_Alarm_Table _2 (A2)
Read number of alarm in alarm table 2 (A2
<= 0x3F)
BINARY
0x0011 + X  Alarms_Total_In_Alarm_Table _X (AX)
Read number of alarm in alarm table X (AX
<= 0x3F)
BINARY
0x0031 Number_of_Active_Alarms_In_Alarm_table _1
Read number of active alarms in alarm
table 1
BINARY
0x0032 Number_of_Active_Alarms_In_Alarm_table _2
Read number of active alarms in alarm
table 2
BINARY
0x0031 + 
(X-1)
Number_of_Active_Alarms_In_Alarm_table _X
Read number of active alarms in alarm
table X
BINARY