4.7.3 Basic Programming Example
For details of the settings in the RECTIFIERS\ CONFIGURE SETTINGS menu, see 6.3.2:
1. Use the navigation arrows to scroll to the item that is to be changed; e.g. FLOAT VOLTAGE.
2. Enter a new value using the CXC virtual numeric keypad, e.g., 54.00.
Download new settings to all connected rectifiers:
3. Click the check mark in the lower right hand corner to return to MAIN MENU navigation screen.
4. Press the OPTION button to evoke the SAVE/LOGOUT pop-up window.
5. Select SAVE to save the new settings or select LOGOUT to clear. A pop-up window appears to
confirm the selection.
4.8 Voltage Mode Status and Temp Comp Settings
The Mode Status displays the current mode of operation:
• Float (FL)
• Equalize (EQ)
• Boost (BST)
• Battery test (BT)
The mode and temperature compensation (TC) appear in the upper left corner. The time duration, until
the mode changes, may also appears in that active area.
Refer to sections 4.9 to 4.12 for a description of the voltage modes.
Mode Status
To change modes:
1. Tap the Mode Status active area to enter the mode selection screen.
2. In the screen that appears, tap the required mode button.
3. Tap the check mark button in the lower right corner to verify the selection and return to the previous
screen.
The icon for the new mode now displays in the upper left corner of the GUI.
Figure 18 Mode selection screen
Mode (+Temp Comp) display 
Mode Selection buttons
Additional functions display
here; such as, countdowns and
status of battery runtime
Battery Voltage and Load Current display
Alarm Indication
Verify action and return
to previous screen
FL + TC
54.00V
250A
Battery Voltage Mode
Periodic Auto-EQ Disabled
Auto BT Disabled
FL
EQ BT
BST