Manual

11031-314-B0-001, Rev. A (12/2012)
1.0 Introduction, continued
1.2 FBE2322Specications
Table 1-3, FBE2322 Cooling Specications
FBE2322 Cooling Specications
Fan Cooling
General Description Two, variable speed, temperature controlled fans.
Airow Capacity (per Fan) 118CFM
Input Power (Volts/Watts) 24 or 48Vdc/20 Watts for 2 Fans
Control Features Dual Fan PCBA w/ Red and Green LED Display
Operation Range (Temp°C/%Speed) 2545°C/50–100%
Alarms Form C dry contact alarm
Condenser High Temp. (76.C/170ºF)
Filter Maintenance
AC Air Conditioner
Capacity Cooling IQ1000V – 1,000 BTUH @ 55ºC (131ºF) ambient
IQ2400VXS – 2400 BTUH @ 55ºC (131ºF) ambient
Heating 400W
Maximum Operating Temperature 5C (131º F)
Electrical IQ1000V –3.1A @ 120VAC/60HZ maximum
IQ2400VXS – 7.5A @ 120VAC/60HZ maximum
High Enclosure Temperature Alarm* 45º C (113 ºF)
Low Enclosure Temperature Alarm* C (32ºF)
Audible Alarm Default Setting* OFF
Digital Display Default Setting* ºC
Filter Maintenance Alarm Setting* Disabled
High Condenser Temperature Alarm* 76.7ºC (170ºF)
Heat Exchanger
Specication 040-025-12-001 040-025-13-001
Nominal Voltage (Vdc) 24 48
FLA (Full Load Amps) 3.5 1.75
Cooling Capacity 30.6W/°C (17W/°F) Cooling @ 65°C (149°F) Ambient Temperature
Operating Temperature Range -40°C–70°C
Maximum Temperature 65°C
Internal Fan Operating Range Off below 5°C; Minimum Speed @ 10°C; Variable to Max. Speed @ 20°C~30°C
Internal Fan Operating Range Off below 15°C; Minimum Speed @ 20°C; Variable to Max. Speed @ 30°C~45°C
High Temperature Alarm 70°C
Low Temperature Alarm -50°C
(*) – Alpha default settings may differ from ICEQube default settings.