Owner's manual

Argus Technologies Ltd. 010-592-C0 Rev G WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Page 15 of 23
6 Operation
6.1 Start-up
1. Apply AC power by a) plugging the unit into AC power outlet, b) turning on the AC feeder breaker, or
c) connecting the IEC (option) to specified source.
2. Verify no alarms are active and the green power indicator is lit.
3. Connect the DC load.
4. Secure the FMPS cover with a padlock or a wire utility tie.
6.2 Normal Operation
Under normal operating conditions, the FMPS delivers 55Vdc (nominal) power for up to two loads. The green
System LED remains lit.
6.3 Status LEDs
The FMPS is equipped with three status LEDs. Refer to the following table:
System (GREEN): Indicates normal mode of operation.
Battery (YELLOW): Indicates power supply is operating from
the battery pack.
Replace Battery (RED): Battery replacement required.
Silence
Alarm
Silence Alarm: Press and hold button one time for 1/2 second
to silence the audible alarm for 24 hours.
Table B–LED and alarm indications
6.4 Battery String LEDs
The FMPS is equipped with two battery string LEDs. The LEDs light when a battery test has failed, suggesting
that battery capacity has fallen below 70 percent.
NOTE: If a single string of batteries is used, the FMPS will report a Battery Missing alarm. This is a normal condition
when using a single battery string.
6.5 AC Fail Alarm
The FMPS sets an AC Fail alarm during an AC line outage or brownout when the AC supply voltage is insufficient
to maintain battery charge. To prevent nuisance alarms and consequent service disruptions, the FMPS monitors
the battery status and sets the alarm when the battery is discharging. Depending on load conditions, it may take
several minutes. The alarm is cleared when the battery receives a consistent charge.
The FMPS also indicates the AC Fail alarm when AC is present, but the system is overloaded to the point that
batteries are required to supplement the power supply in meeting load requirements. If an AC Fail Alarm is
indicated despite a solid AC line voltage, then verify the load is within specification and lead lengths and wire
sizes are accordant with the installation instructions.