Owner's manual

Specifications for Argus Technologies’ FMPS Continued
Argus Technologies Ltd. 010-592-B1 Rev A WC
Printed in Canada. © 2008 Argus Technologies Ltd. ARGUS is a registered trademark of Argus Technologies Ltd. All Rights Reserved. Page 4 of 5
Dimensions
Battery Run Times
ONE STRING
Run Time (hours) vs. Temperature
Watts -10°C 0°C 25°C 40°C
20
14.4 15.6 18.7 20.0
40
7.0 7.4 8.9 10.0
60
3.9 4.8 6.6 7.2
80
2.7 3.1 4.3 5.5
100
2.2 2.5 3.2 3.7
120
1.8 1.9 2.6 2.9
150
1.5 1.7 2.0 2.3
TWO STRINGS
Run Time (hours) vs. Temperature
Watts -10°C 0°C 25°C 40°C
20
21.7 22.5 24.4 25.0
40
14.1 15.6 18.7 20.0
60
9.0 9.6 13.1 15.5
80
6.7 7.4 8.9 10.0
100
5.9 6.3 7.5 7.9
120
3.7 4.8 6.7 7.2
150
3.0 3.3 5.0 6.2