Specifications
39
017-230-B0 Rev 0810
6.9.8 Viewing the Serial Number
To display the serial number of the Alpha FXM UPS, type "∗QY0" at the command line and press "Enter".
6.9.9 Setting the Peukert Numbe r and Capacity
You can set the Peukert Number and Capacity using the RS-232 interface or the web interface. To display the
current Peukert Number, type "∗QY6" at the command line and press "Enter".
To change the Peukert Number to 1.1345, type "∗ST6:1.1345" at the command line and press "Enter".
To display the current Peukert Capacity, type "∗QY7" at the command line and press "Enter".
To change the Peukert Capacity to 109.123, type "∗ST7:109.123" at the command line and press "Enter".
To determine the Peukert number and capacity of your battery, refer to "Puekert Number and Battery Capacity".