Specifications

39
017-230-B0 Rev 0810
6.9.8  Viewing the Serial Number
To display the serial number of the Alpha FXM UPS, type "QY0" at the command line and press "Enter".
6.9.9  Setting the Peukert Numbe r and Capacity
You can set the Peukert Number and Capacity using the RS-232 interface or the web interface. To display the
current Peukert Number, type "QY6" at the command line and press "Enter".
To change the Peukert Number to 1.1345, type "ST6:1.1345" at the command line and press "Enter".
To display the current Peukert Capacity, type "QY7" at the command line and press "Enter".
To change the Peukert Capacity to 109.123, type "ST7:109.123" at the command line and press "Enter".
To determine the Peukert number and capacity of your battery, refer to "Puekert Number and Battery Capacity".