Specifications
55
017-230-B0 Rev 0810
Figure 35 — User Input Configuration: Setting the Trigger Type
Figure 36 — User Input Configuration: Setting the Logic Level
Figure 37 — User Input Configuration: Setting an Action
2. In the Input 1 column, select the Type down arrow to display the 3 types of available triggers: Edge Trigger,
Level Toggle, and Level Alternative. For more information on how triggers work, see "Types of Trigger".
3. Select Edge Trig ger.
4. Select Low from the Level drop down menu. The User Input will go to logic level "low" whenever it is
triggered.
5. Select User Alarm On from the Action #1 drop down menu.
6. Click the Update button and enter the password to confirm if required.
Procedure
1. Select UPS Maintenanc e > User I nput to display the Us er Input Configurat ion window.