Table V Electrical Specications
Parameter Value
Battery Charger Current, 
Amps
FXM 650-48/1100/2000: 48 VDC.
Battery Charger Temperature 
Compensa tion
8
-5 mV/°C/Cell (factory default), user adjustable to -2.5, -4, -5 or -6 mV/°C/Cell.
Battery type
Anderson Power mating part SB50 or equivalent.
Table W  —  Boost/Buck/Line Transfer Thresholds
Parameter Value
120 VAC Units 230 VAC Units
High Line Transfer
High Line Retransfer
175 VAC
162 VAC
325 VAC
303 VAC
Buck 2 Transfer
Buck 2 Retransfer
152 VAC
146 VAC
282 VAC
272 VAC
Buck 1 Transfer
Buck 1 Retransfer
134 VAC
128 VAC
250 VAC
236 VAC
Boost 1 Retransfer
Boost 1 Transfer
116 VAC
112 VAC
210 VAC
207 VAC
Boost 2 Retransfer
Boost 2 Transfer
102 VAC
98 VAC
180 VAC
176 VAC
Low Line Retransfer
Low Line Transfer
97 VAC
88 VAC
162 VAC
151 VAC
Table X Regulatory
Parameter Value
Electrical Safety
UL 1778, CSA 107.3, EN 62040-1-2, EN60950-1.
Emission
FCC Part 15, Subpart B, Class A, CSPR22, EN55022 Level A.
Marks
C
CSA
US
, CE (230 VAC versions only).
Packaging
Designed to meet requirements for ISTA program.
7. Efciency is measured at an ambient temperature of 25°C, full resistive condition and nominal Line and Battery voltage.