Specifications

10
UPS Control Modules
Caltrans FXM UPS
Rugged UPS Module
> The Caltrans FXM UPS has all the benefits of the standard FXM UPS plus:
• Caltrans approved, TEES 2009
• 4 lines LCD display
• Resettable output circuit breaker
• Input/Output, with quick disconnects and locking device
Electrical
>120Vac Model
Battery string voltage: .......48Vdc
Nominal voltage: ...............120Vac
Nominal frequency: ...........Auto-sensing
Input:
Current: ........................... 9.8A nominal
Voltage: ..........................85 to 175Vac
Output:
Voltage regulation: .........+/- 10% over input voltage range
Power at 50°C:................1100W/ VA
Display
The LCD control panel provides "at a glance" monitoring. This panel when
used along with the CANCEL, SCROLL and SELECT buttons, allows you to
program, make measurements, and troubleshoot the Alpha FXM.
LCD Screen
A. IP: Input voltage reading
B. OUT: Output voltage reading
C. FLT: Battery voltage when not charging
CHR: Battery voltage when charging
D. BAT: Battery capacity (0-100%)
E. Present operating mode (Line mode shown)
F. Text "ALARM" flashes if alarm triggered
G. RELAY: Energized relays numbers
H. Text "FAULT" flashes if fault triggered
Mechanical
Dimensions:
mm: ................................. 133H x 394W x 222D
inches: ............................5.22H x 15.5W x 8.75D
Weight: ..............................16kg (35lbs)
Environmental
Operating temp range*: .....-40 to 74°C (-40 to 165°F)
Audible noise @ 25°C: ......45dBa @ 1 meter (39in)
*Derates after 5C
Performance
Typical output voltage THD: ........ <3%
Typical efficiency: ...................... >98% (resistive load)
Typical transfer time: ................. <5ms
MTBF:
@ 0.0°C: .......................... 246,206 hrs
@ 25.0°C: ........................174, 955 hrs
@ 50.0°C: ........................103,030 hrs
Power Connector Options
Agency Compliance
Electrical safety: ................UL1778, CSA 22.2 No 107.3-03
Marks: ...............................
C
CSA
US
,CE**
EMI: ...................................Class A FCC/CISPR
[EN 50091-2:1995]
*Ethernet SNMP card is standard on the 120Vac model and optional on the 230Vac model
**CE applies to 230Vac version only
120Vac Model
Input Output
IEC* IEC*
* FXM models with IEC connectors come with 4 lines LCD display instead of the traditional 2 lines display
Consult your Alpha representative for P/N configurations