Specifications
17
Enclosures
Multi-Mount Outdoor
Enclosure - Traffic
Outdoor Enclosure
> Designed for outdoor or secure indoor applications
> Traffic grade aluminum enclosure protects battery backup power systems from outdoor elements
> Various mounting options (including pole-mount) provide a flexible solution for space constrained traffic applications
> Large sun shield reduces solar heat load inside cabinet
> Thermostat controlled fan and louvered vents ensure reliable operation in high temperatures
> 180° stainless steel piano hinged door makes installation and maintenance easy and convenient
> Three-point latching mechanism with Corbin Type 2 lock for maximum security
Consult your Alpha representative for P/N configurations
Mechanical
Dimensions:
mm: ................................. 687H x 559W x 457D
inches: ............................27H x 22W x 18D
Weight: ..............................27.2 kg (6 0 lb s)
Construction: High strength corrosion resistant 0.125"
thick aluminum
Finish: ................................ Natural aluminum
Equipment space: ............. 7RU space with one battery shelf
Equipment rails: ................ EIA standard 19"
Cable entrance:
Bottom of enclosure: ......1 x 3" diameter knock-out (2½" trade size)
4 x 1.125" diameter knock-out (¾" trade size)
Rear of enclosure: ...........4 x 1.125" diameter knock-out (¾" trade size)
Hardware
Hinge type: ........................Stainless steel piano hinge
Door prop: .........................Aluminum rod, 2 locking open positions
Door latch: ......................... 3 point latch with integrated Corbin Type 2 lock
HVAC
Cooling: ............................. Thermostat controlled 48Vdc fan, 100 cfm or
better, ON at 49°C (120°F) Off at 32°C (89°F)
Ventilation: ........................Door installed louvers
Environmental
Temperature:
Operating: ......................-40 to 46°C (-40 to 115°F)
Storage: ..........................-40 to 85°C (-40 to 185°F)
Installation
Access:.............................. Front hinged door provides full front access
Maintenance
Door installed louver: ........ Equipped with washable filter
Enclosure Options
Mounting: .......................... Pole, host, wall, or pedestal
System Specifications (as shown)
• Battery shelf with 4x AlphaCell™ 85GXL batteries
• FXM2000 UPS
• Universal automatic transfer switch
>System Options
• Universal generator transfer switch
• AlphaGuard battery balancer
• Battery heater mats
• Transient voltage surge suppression device
Agency Compliance
NEMA rating: .....................3R