Specifications
6
UPS Control Modules
Rugged UPS Module
> 350 W/VA UPS module designed to operate in extreme environments and provide maximum flexibility while ensuring
critical loads remain protected and running during power outages and other power disturbances
> Unsurpassed flexibility with dual 120Vac & 24Vac outputs
> Wide range Automatic Voltage Regulation (AVR) lengthens battery life by providing protection without transferring to
backup mode during voltage surge or sag
> Local and remote monitoring and control via USB port and Ethernet SNMP interface
> Temperature compensated battery charging protects batteries from overcharging or undercharging at extreme
temperatures, extending the life of the battery
> Independently programmable control and report dry contacts allow monitoring and controlling of key functions
Consult your Alpha representative for P/N configurations
Electrical
>120Vac Model
Battery string voltage: .......48Vdc or 24Vdc
Nominal voltage: ...............120Vac
Frequency: ........................60/50Hz ±5% (auto-detection)
Input:
Voltage range (w/o transferring to battery mode): 88 to 152Vac
Current:
• FXM350-24: .................5.3A
• FXM350-48:.................5.7A
Output:
Waveform:.......................Pure sinewave
Nominal voltage: ............Dual 120Vac, 24Vac
Voltage regulation: .........±10%
Power at 50°C:................350W/VA Total
• 24Vac: ..........................260W/VA (max)
• 120Vac: ........................350W/VA (max)
Frequency: .....................Output frequency = Input frequency
>230Vac Model
Battery string voltage: .......24Vdc
Nominal voltage: ...............230Vac
Frequency: ........................60/50Hz ±5% (auto-detection)
Input:
Voltage range (w/o transferring to battery mode): 151 to 282Vac
Current: ........................... 2.7A
Output:
Waveform:.......................Pure sinewave
Nominal voltage: ............230Vac, 24Vac
Voltage regulation: .........±10%
Power at 50°C:................350W/VA Total
• 24Vac: 260VA (max)
• 230Vac: 350VA (max)
Frequency ......................Output frequency = Input frequency
Mechanical
Mounting: .................................. 19" or 23" rack with the addition of ears for
rack mounting
Dimensions:
mm: ......................................... 88.14H x 341.88W x 211.74D
inches: .................................... 3.47H x 13.46W x 8.34D
Weight: ...................................... 8.62kg (19lbs)
Environmental
Operating temp range: .............. -40 to 74°C (-40 to 165°F)
Audible noise @ 25°C: .............. <45dBa @ 1 meter (39in)
Performance
Typical output voltage THD: .. <3%
Typical efficiency .................... >96%
Typical transfer time ............... <5ms
Power Connector Options
Agency Compliance
Electrical safety: ................ UL1778, CSA C22.2 No. 107.3,
EN60950-1, EN62040-1-2
Marks: ............................... cCSAus, CE*
EMI: ................................... FCC Part 15/B, EN55022. Class A.
EN62040-2
*CE applies to 230Vac version only
120Vac Model
Input Output
Standard
Terminal
Block
Terminal
Block
230Vac Model
Standard
Terminal
Block
Terminal
Block
FXM 350