MiniMax Power Supply Installation and Operation Manual 60V/9A and 60V/15A Output Models Effective: November, 2003 ® Alpha Technologies
Power Alpha Technologies. Protecting The Power in Communications.
MiniMax Power Supply Installation and Operation Manual 60V/9A and 60V/15A Output Models 164201241-001 Rev. C0 © 2003 Alpha Technologies NOTE Photographs and drawings contained in this manual are for illustrative purposes only. These photographs and drawings may not exactly match your installation. NOTE Review the drawings and illustrations contained in this manual before proceeding.
MiniMax Power Supply Installation and Operation Manual Table of Contents Warnings & Cautions ............................................................................................ 5 1. Introduction ....................................................................................................... 6 1.1 Overview .............................................................................................. 6 2. Specifications ........................................................................
WARNINGS & CAUTIONS A “Warning” identifies conditions and actions that pose a hazard to the user. A “Caution” identifies conditions and actions that may damage the power supply or associated equipment. WARNING This power supply and its associated hardware (enclosure, cabling) may contain equipment(s), or parts which have accessible hazardous voltage or currents. To avoid injury: • This power supply and its associated hardware must be serviced by authorized personnel only.
1. Introduction 1.1 Overview This manual provides information related to the installation, operation and service of specific equipment. For assistance regarding personnel training, specific problems, or questions relating to applications, please call Alpha Technologies. The information contained in this manual is restricted to customers of Alpha Technologies, and use by unauthorized personnel is strictly prohibited.
2. Specifications 2.1 Electrical & Mechanical Specifications 120 VAC MODELS Outdoor Pole and Ground Mount ELECTRICAL SPECIFICATIONS PSF-MXP-AXX, PSF-MXG-AXX PCS-MXP-111, PCS-MXG-111 120 Vac, 60Hz (+15% / -20%) Input Voltage Input Current (@ 60V, 15A Nominal) 5A 9A 60Vrms Quasi-square wave ±3% Output Voltage Output Current Operating Environment 9A (maximum) 15A (maximum) 88% (minimum) Full Load Efficiency (typical) Output Pow er PCS-MXP-113, PCS-MXG-113 PCS-MXP-114, PCS-MXG-114 900VA max.
2.1 Electrical & Mechanical Specifications, continued 230VAC, 50Hz (CE) MODELS Indoor/Wall Mount ELECTRICAL SPECIFICATIONS PSF-W00-D09 PSF-W00-D15 Input Voltage 230 Vac, 50Hz +15% / -20% 230 Vac, 50Hz +15% / -20% Input Current (@ 60V, 15A Nominal) 3.0A 4.
3. Installation Pole Mounting (Models PSF-MXP-*** and PCS-MXP-***) 3.1 A bucket truck or other suitable equipment such as spikes and safety harnesses, should be used during installation or service of pole-mounted cabinets. To mount the MiniMax power supply to a utility pole, perform the following steps: NOTE Pole mounting the cabinet should be done in accordance with the local agreement between the cable operator and the utility company. 1.
3. Installation Pole Mounting (Models PSF-MXP-*** and PCS-MXP-***), continued 3.1 2. Remove all equipment, hardware, and options from the cabinet and store in a secure location for future use. 3. Remove the U-shaped mounting bracket from the cabinet rear panel. 4. Use the bracket as a template to mark mounting holes at the desired mounting location. If possible, position the cabinet so the front panel is easily accessible. 5. Drill 11/16" holes in the pole at the marked locations. 6.
3. Installation Ground Mounting (Models PSF-MXG-*** and PCS-MXG-***) 3.2 Although ground mounting the power supply can be accomplished by several methods, the following procedure is recommended. 1. 2. Select an appropriate site. Remove the turf and level an area of approximately 36" x 36". In accordance with local codes, install the disconnect box near the AC power source.
3. Installation Ground Mounting (Models PSF-MXG-*** and PCS-MXG-***), continued 3.2 5. Attach the ground mounting brackets from the supplied kit to the ground skirt using the 5/16-18 x 3/4” screws and the 5/16"-18 nuts. 6. Make a template from sheet metal or wood indicating the position of the ground mounting bracket mounting holes. Drill out the four holes in the template and insert two customer-supplied 5/8" x 4" bolts.
3. Installation 3.3 Electrical Connections for Pole and Ground Mounts WARNING Verify the utility disconnect is off and that no conductors are energized before proceeding. 1. Open the housing cover and place a screwdriver blade in the small notch at the top of the housing to hold the cover in place. 2. Install a liquid tight conduit to the fitting on the cabinet bottom and pull the AC primary wiring in to the cabinet housing. 3.
3. Installation 3.3 Electrical Connections for Pole and Ground Mounts, continued 1.25” Brass Seizure Screw 8. Screw the cable connector into the output port (large hex nut fitting) located on the baseplate of the APC2. Make sure that the center pin extends far enough into the fitting so that the seizure assembly can be secured. Hex-nut Fitting 9. Tighten the brass seizure screw on the cable “stinger” or center conductor.
3. Installation Wall Mounting and Electrical Connection (Models PSF-W00-D**, PSF-W00-D09, and PSF-W00-D15) 3.4 NOTE The MiniMax non-standby power supply must be installed in accordance with local building codes to prevent damage to the mounting structure and the unit itself. 1. Install an agency-approved service disconnect switch with overcurrent protection, between the AC power source and the cabinet mounting point. Wire to power line in accordance with local codes. 2.
3. Installation Wall Mounting and Electrical Connection (Models PSF-W00-D**, PSF-W00-D09, and PSF-W00-D15), continued 3.4 6. Connect the electrical service to the to terminal block located inside the unit, as shown in figure 3-7. N/C 60 VAC Out N L Fig. 3-7 Terminal Block Connections 16 7. Connect the CATV coax cable to the type G2 connector on bottom of the enclosure. (Refer to figure 3-2.) 8. Test installation according to requirements.
4. Operation 4.1 Initial Turn Up 1. Turn the utility disconnect ON. The green lamp should light, indicating power output. Power will be applied to the cable plant at this time. 2. If desired, the output voltage can be checked at the cable center conductor seizure clamp and the cable ground, using a true RMS AC voltmeter.
Power www.alpha.com Protecting The Power in Communications. Alpha Technologies Ltd. 4084 McConnell Court Burnaby, BC, V5A 3N7 CANADA Tel: (604) 430-1476 Fax: (604) 430-8908 Alpha Technologies Europe Ltd. Cartel Business Estate Edinburgh Way Harlow,EssexCM202TT UNITEDKINGDOM Tel: +44-1279-422110 Fax: +44-1279-423355 Alpha Technologies Hansastrasse 8 D-91126 Schwabach GERMANY Tel: +49-9122-79889-0 Fax: +49-9122-79889-21 Alphatec 339 St.