Up to 100 events are stored in the UPS’s log. If more than 100 events occur, the oldest is over
written.
Procedure
1. To see the log, type event (all lower case) and press ENTER. The events are listed
starting with the most recent and appear as:
eventX=12/25/99 01:45:59 0000000000000000, 0000000000000000, 000
2. If less than 100 events occurred, the last entry appears as:
eventX=00/00/00 00:00:00 0000000000000000, 0000000000000000, 000
3. To clear the log, type eventclr and press ENTER.
It takes the UPS 30 seconds to clear the log. Do not enter any other commands during this
time.
4. To see a specic event, type eventX where X is from 1 to 100 and press ENTER. To see a
range of events (for example, events 20 to 30), type eventX-X where X are events from 1
to 100 and press ENTER.
Finished
A5 Accessing the 100-Event Log
Event #
Date Time
Alarm Fault Mode
For details on these readouts, see below.
Code Mode Code Mode Code Mode
000 Standby 003 Boost 1 006 Inverter
001 Line 004 Buck 1 009 Shut down
002 Boost 2 005 Buck 2 010 Bypass
Fault: When the following bits show a 1, it
is displaying the following faults.
Alarm: When the following bits show a 1,
it is displaying the following alarms.
Fan Fail
Battery Test
User Input
Weak Battery
Appendix
Doc# 017-220-B0 Rev. 01 / 07 21