Dry Contacts (Models 300 & 600 only)
Contacts C1 and C2 allow you to connect the UPS to an external monitoring panel or to
trafc control equipment.
The factory default settings are given below, but you can program them to meet your
requirements (See Section 4.4, “Programming the Dry Contacts” or Section 4.6, “Novus
Micro Graphical User Interface”.
Figure 1.3.8 shows the contact’s layout.
C1: This contact is energized when Line power is unqualied and the UPS provides
backup battery power to the load(s). It is called the “On Battery” contact.
C2: This contact is energized when the battery drops below a preset voltage
level. It is called the “Low Battery” contact. You have the option to change the pre-
programmed level to match the batteries used and the actual operating conditions.
See Section 4.3, “Adjusting and Controlling the UPS, #35 Low Battery Warning
Voltage” for more details.
The dry contacts
have a maximum
rating of 1A at 250V.
Microprocessor
UPS
Interior
Normally
Closed (NC)
Normally
Open (NO)
Common (C)
Figure 1.3.8 – Dry Contact Layout (Standard for C1 & C2)