Operator`s manual

2.3 Wiring the UPS
DANGER: Before starting, make sure line power is turned off and that the UPS’s
battery and input circuit breakers are turned off.
If stranded wires are used to connect the input and output terminal blocks, ferules
or equivalent crimping terminals must be used.
Separate the Input power cables from the Output power cables within the UPS
enclosure. Route them through separate conduit openings as they exit the UPS.
Separate the DC Battery cable from the AC Input and Output power cables. Route
the cable through its own opening.
Tools and Materials Required
Hammer for removing the knockouts.
A slot head screwdriver to t the front panel dry contact terminal blocks and a slot head
screwdriver for removing the knockouts.
DC voltmeter.
High strength, water-resistant tape (such as duct tape).
Battery terminal corrosion inhibitor (such as NOCO Company’s NCP-2 or Sanchem Inc.’s
No-Ox ID Grease “A”).
Maximum of 12 AWG wire for wiring the input and output terminal blocks.
If used,
1
/
2
inch conduit connectors to t the knockouts (
7
/
8
inch diameter) and armored
conduit to t.
Optional battery heater mats.
16
Novus Micro Operators Manual
Doc# 017-221-B0 Rev 0307