Operator`s manual
Step 1: Connecting the UPS to the Line and
Load
1. Remove the front cover (lift it up and then pull
out at the bottom).
2. If necessary, remove the knockouts using a
hammer and screwdriver.
Note: If you have more than one battery
cabinet installed, you will have to remove the
knockouts on each shelf.
3. If used, install conduits into the holes.
4. Install the wires into the cabinet.
5. Strip the ends of the wires by
7
/
16
inch (11mm).
6. Secure the wiring to the wiring management
panel with tie-wraps provided with the UPS.
Make sure that the wiring is long enough to
reach the terminal blocks.
DANGER The input and output wiring
must NOT touch the cabinet except for
the wiring management panel.
DANGER: Each terminal block has two inputs for each pole (line, neutral and
ground). Make sure you have inserted each wire into the correct position and not
accidentally connected the line and neutral to the same pole.
DANGER: Verify the line wire is attached to the line terminal block, the ground
wire is attached to the ground terminal block and the neutral wire is attached to
the neutral terminal block to prevent accidental shocks or electrocutions.
7. Push in the button on the output terminal
block and then insert the wire into the
terminal block until no uninsulated wire
is visible. Repeat until all the wires are
installed.
8. Repeat step 7 above for the input terminal
block.
Proceed to Step 2: “Installing and Wiring
the Batteries.”
CORRECT
INCORRECT
Remove knockouts as needed.
Install conduits if used.
Secure wiring
to backing
plate with tie
wraps.
Alternate routing
for output wiring.
Push button down to insert
wires into terminal block
17
Installation
Doc# 017-221-B0 Rev 0307