Operator`s manual

3.5 Making Measurements
The System Status Menu (Figure 3.5.1) on Model 1000 lets you make measurements of
various UPS inputs, outputs, temperatures and other values. On all models, you can use the
Novus FXM Monitor software to make these measurements (See Section 4.6, “Novus FXM
Graphical User Interface”).
Procedure
1. From the logo screen (Figure 3.2.1) go to
the system status menu (Figure 3.2.3).
2. Press the SELECT button to enter the
submenu (Figure 3.5.1).
3. Press the SCROLL button to move
between items in the submenu. When
you reach the item you want to measure,
stop pressing the button.
The measurement is automatically
displayed on the LCD. It is automatically
updated every 0.5 second (VIN shown).
Measurement Finished
System Status Menu
LCD Shows Meaning Description
VIN Input Voltage The line input voltage into the UPS.
VOUT Output Voltage The UPS’s output voltage (true RMS).
IOUT AC Output Current (AC) The UPS’s AC output current (true RMS).
BATT TEMP Battery Temperature The battery’s temperature (°C).
FREQ IN Input Frequency The frequency of line power into the UPS (Hz).
OUTPUT PWR Output Power The UPS’s output power in VA (true RMS).
BATT VOLT Battery Voltage The battery’s output voltage (VDC).
CHGR CUR Charger Current The UPS’s battery charging current is set to this value (Amps).
DATE Date The date and time (24 hour clock).
TIME Time
INV COUNT Inverter Count The number of times the UPS was in inverter mode.
INV TIMER Inverter Time The total amount of time the UPS was in inverter mode.
SHED TIMER1 Amount of time until
the dry contact is
activated.
The factory default dry contact for this setting is contact C4. SHED TIMER2 and SHED
TIMER3 can be eld programmed (See Section 4.4.1, “Programming the Dry Contacts”).
This display shows the amount of time left (in seconds) until the contact is activated. The
factory default setting is 2 hours, but this can be changed as shown in Section 4.4.1.
SHED TIMER2
SHED TIMER3
VERSION Software Version The software version used in this UPS.
Figure 3.5.1
System Status Menu
STATUS
MENUS
120/60/N
LINE
CANCEL
SCROLL
SELECT
VIN
120V
120/60/N
LINE
Novus Micro Operator’s Manual
Doc# 017-221-B0 Rev 03/07 28