3.7 Viewing the 25-Event Log
The event menu displays on the LCD the last 25 events the UPS went through and the
malfunction that triggered it. If more than 25 events occur, the oldest is overwritten. To clear
this log, see Section 3.4, “Operating the UPS, INV RECORD.”.
To see the last 100 events, go to the RS-232 100-event log (See Section 4.5, “100-Event Log”
or Section 4.6, “Novus User Software, Event History”.
Procedure
1. From the Logo Screen (Figure 3.2.1) go
to the EVENT STATUS MENUS (Figure
3.2.3).
2. Press the SELECT button to enter the
submenu.
3. The log screen appears on the LCD
screen.
4. Press the SELECT button. The event
counter ashes.
5. Press the SCROLL button to scroll
through the event counter.
6. When you reach the event you want,
press the SELECT button.
The event loading screen appears and
then the log screen reappears with the
details for that event.
Press the SCROLL button again to see
if more than one fault or alarm happened
at the same time. Keep pressing the
SCROLL button until you return to the
initial log screen.
Finished
EVENT STAT
MENUS
120/60/N
LINE
ALARM STATUS
DATE EVENT HAPPENED
(YY:MM:DD)
TIME EVENT HAPPENED
(HH:MM:SS 24-hour clock)
EVENT COUNTER
(Event #1 shown)
OPERATING MODE THE UPS WAS IN WHEN
THE EVENT HAPPENED (Line shown)
06:11:29
16:23:56
EVENT: 1
LINE
CANCEL
SCROLL
SELECT
EVENT: 1
Event
Loading
Doc# 017-221-B0 Rev 03/07 31
Operation