Operator`s manual
4.2.2 RS-232 Menu Tree
Submenus 1, 2 and 4 provide read-only screens for monitoring the UPS. To control the UPS,
use submenu #3, the Maintenance submenu.
Doc# 017-221-B0 Rev 03/07 35
Communication
1-Unit Specications
Unit Model
Input
Voltage
Frequency
Output
Voltage
VA
Battery Voltage
Voltage
Software Version
2-Input/Output Values
Input
Voltage
Frequency
Output
Voltage
Current
VA
Battery
Voltage
Temperature
3-Maintenance
(Section 4.3)
30-Battery Test Options
300-Set Battery Test Period
301-Battery Test On/Off
31-Inverter On/Off
310-Set Inverter-Off Delay
311-Inverter On/Off
32-Change Password
34-Line Qualify Time
1) Set to 3 seconds (Default)
2) Set to 10 seconds)
3) Set to 20 seconds
4) Set to 30 seconds
5) Set to 40 seconds
6) Set to 50 seconds
35-Low Battery Warning
Voltage
36-Load Shed Timer
On/Off
1) Timer 1 on
2) Timer 1 off
3) Timer 2 on
4) Timer 2 off
5) Timer 3 on
6) Timer 3 off
4-Line Slow
Detection Setup
This read-only screen
shows the UPS’s input
voltage parameters. These
values are factory set and
cannot be changed in the
eld.
Figure 4.2.2
RS-232 Menu Tree
0-Main Menu
(Figure 4.2.1)
Press ENTER to go up 1 level
in the menu tree.
To reach any submenu, type
in its number and press
ENTER.
To reach the main menu, type
0 and press ENTER.
These 2 read-only screens show the UPS’s
factory specications or the present input and
output measurements. The Input/Output Values
submenu does not automatically update. For an
updated value, type 2 and press ENTER.
Submenus Submenus