Enter command UPS display Description
Setting the Timer
timer=00:01:00 and press Enter *timer=00:01:00 Sets the value of timer1 to 60
seconds.
timer=120
and press Enter *timer=120
timer1=00:01:00 and press Enter *timer1=00:01:00 Sets the value of timer1 to 60
seconds.
timer1=120
and press Enter *timer1=120
timer2=00:01:00 and press Enter *timer2=00:01:00 Sets the value of timer2 to 60
seconds.
timer2=120
and press Enter *timer2=120
default and press Enter *default Resets the timer to the fac-
tory default of 02:00:00 (2
hours); and resets contacts C1
and C2 to the factory default
settings.(See Section 4.4.1,
“Programming the Dry Con-
tacts.”)
Note: In the above example, the default timer setting of 2 hours is used.
* Indicates that the UPS has responded to the command you entered.
Time can be entered in units of 0.5 second; e.g. 120 units of 0.5 seconds = 60 seconds. However, it is more intuitive to
enter time in the hh:mm:ss format, such as 00:01:00 for 1 minute or 60 seconds in the above example.
4.4.2 Setting the Date and Time
Enter command UPS display Description
clock and press Enter *clock=12/31/07 22:00:00 Returns the value of timer1
clock=010107120000
and press Enter
*clock=01/01/07 12:00:00
Sets the date and time to Jan 01,
2007, 12:00pm.
Note: Time is displayed in the 24 hours clock format. Changing the mm/dd/yy format with DATE SEL on the LCD Control
Menu (Figure 3.4.1) does not change the RS-232 mm/dd/yy format.
* Indicates that the UPS has responded to the command you entered.
If the date or time change is invalid, the UPS will return the time and date it was set to before you tried making the
change. The date and time must be entered as one complete line command; you cannot change only the time or the date
alone, both must be set at the same time. If you make a mistake, press ENTER and try again.