Operator`s manual
6. Type (all lower case) oad(1 space);b
and press ENTER.
A pop-up appears asking you to locate
the new rmware. Look for a “sx record”
(*.sx). Select this new rmware. The oad
pop-up appears.
When the software is nished loading into
the UPS, the pop-up shows “Loaded OK:
xx seconds.”
7. Type (all lower case) exit and press
ENTER.
The uBug12 screen disappears. Turn the
UPS off.
8. Turn the UPS on.
If the reprogramming was successful, the
LCD’s logo screen appears. If it wasn’t, it
shows “Alpha XP ISP” as shown in step
2. Try installing the rmware again.
Firmware Replacement Finished
1: Type oad ;b.
2: Look for a .sx le.
Firmware is loaded.
Alpha
120/60/N
LINE
Novus Micro Operator’s Manual
Doc# 017-221-B0 Rev 03/07 48