Operator`s manual
Boost/Buck/Line Transfer Thresholds
Subject to change without notice
Model 300 Model 600 Model 1000
Parameter 120VAC 230VAC 120VAC 230VAC 120VAC 230VAC
Buck 1 to INV
INV to Buck 1
151 VAC
146 VAC
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Buck 2 to INV
INV to Buck 2
N/A
N/A
325 VAC
314 VAC
169 VAC
162 VAC
318 VAC
306 VAC
169 VAC
162 VAC
325 VAC
314 VAC
Buck 1 to Buck 2
Buck 2 to Buck 1
N/A
N/A
281 VAC
275 VAC
151 VAC
146 VAC
283 VAC
275 VAC
148 VAC
146 VAC
282 VAC
272 VAC
Line to Buck 1
Buck 1 to Line
131 VAC
126 VAC
250 VAC
244 VAC
132 VAC
128 VAC
251 VAC
240 VAC
129 VAC
126 VAC
250 VAC
236 VAC
Boost 1 to Line
Line to Boost 1
116 VAC
112 VAC
214 VAC
209 VAC
115 VAC
111 VAC
212 VAC
209 VAC
114 VAC
109 VAC
210 VAC
207 VAC
Boost 2 to Boost 1
Boost 1 to Boost 2
102 VAC
98 VAC
186 VAC
180 VAC
97 VAC
101 VAC
182 VAC
177 VAC
102 VAC
87 VAC
182 VAC
175 VAC
INV to Boost 2
Boost 2 to INV
92 VAC
87 VAC
163 VAC
158 VAC
92 VAC
86 VAC
158 VAC
152 VAC
93 VAC
85 VAC
160 VAC
153 VAC
Regulatory
Electrical Safety UL 1778, CSA22.2#107.3,
EN50091-1-2, EN60950
Emission
†
FCC subpart J, level A for
conducted and radiated EMI;
CSPR22, EN55022 level A for
conducted and radiated EMI.
Marks
C
CSA
US
, CE (CE for 230VAC
versions only).
Packaging Designed to meet requirements
for ISTA program
†
The Novus Micro generates, uses and radiates radio
frequencies if not installed and tested in accordance with
the instructions in this manual. It has been tested and
found to comply with the limits established for a Class
A computing device pursuant to part 15 of FCC rules
and CSPR 22 when it is operated alone. It also complies
with the radio interference regulations of DOC which are
designed to provide reasonable protection against such
interference to radio to TV reception, which is determined
by switching it on and off, relocate the equipment or use
an electrical circuit other than the one used by the Novus
Micro.
Notes:
1. Above 50°C ambient, derate output power by 1.1% per
°C rise, up to 74°C max.
2. Capable of operating at fully rated power below 0°C
down to -40°C after the UPS has been stabilized at 0°C
for at least 1 hour.
3. Derate 2°C per 1000 ft (305 m) above 4500 ft (1372 m).
4. The LCD may not function below -15°C. It resumes
normal operation when the temperature rises above
-15°C. The UPS continues to operate normally.
5. CAUTION: Risk of electric shock and re hazard,
replace fuse with the same type and rating
Novus Micro Operator’s Manual
Doc# 017-221-B0 Rev 03/0750