Manual

21031-161-B0-006, Rev. F
2.0 Installation, continued
2.2
Ground-mount Installation: PWE-4, PWE-8, PWE-9, PWE-D36
Never transport the unit with installed batteries. Doing so can cause injury to the installer, or
damage the enclosure and equipment. Install the batteries after you transport the unit to the site
and secure it to the pad.
CAUTION!
ATTENTION:
It is the responsibility of the installer to meet the requirements of all applicable national and local codes. Alpha
Technologies assumes no responsibility or liability for failure of the installer to comply with the requirements of
all applicable local and national codes.
2.2.1 Pre-Installation
Before choosing a location and beginning installation, consider the following:
Provide adequate room for service personnel to remove the doors for battery
installation and removal.
Wherever possible, select a site that is above the 100-year ood plain and away
from residences.
Locate in the shade to minimize the effects of solar loading.
Locate in an area with good air ow.
Locate away from sprinkler systems or other sources of forced water.
Locate out of the prevailing wind to minimize the buildup of snow or accumulation
of wind-borne dust.
Avoid locating the enclosure where it will be an obstruction or will inhibit visibility.
Evaluate the soil conditions for suitability for the installation of the grounding
system applicable to your particular installation.
Is utility power cabling run to and terminated at the site?
NOTE:
The appropriate grounding method for a particular location depends on soil type, available space, local codes,
NEC (National Electric Code), and other site-speci c characteristics.